KENT, WA —
OSHA Inspection: BONNEVILLE POWER ADMINISTRATION-COVINGTON DISTRICT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BONNEVILLE POWER ADMINISTRATION-COVINGTON DISTRICT in 28401 COVINGTON WAY SE, KENT, WA 98042 (NAICS 221121). OSHA activity number 342296589.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BONNEVILLE POWER ADMINISTRATION-COVINGTON DISTRICT
- Site address
- 28401 COVINGTON WAY SE
- City
- KENT
- State
- WA
- ZIP
- 98042
- Mailing
- 28401 COVINGTON WAY SE, KENT, WA 98042
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221121
- Employees
- 28
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.147 C04 I
- Issued
- May 26, 2017
- Abate by
- Jul 14, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in the activities covered by this section: a) Facility, where employees performed preventative maintenance and repairs on building equipment such as, but not limited to, ballast in lighting fixtures and the hardwired Champion air compressor.
Recent events (1)
- — Z (S) $0
1910.147 C06 I
- Issued
- May 26, 2017
- Abate by
- Jul 14, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i):The employer did not conduct a periodic inspection of the energy control procedure(s) at least annually to ensure that the procedure and the requirements of this standard are being followed: a) Facility, where employees performed preventative maintenance and repairs on building equipment such as, but not limited to, ballast in lighting fixtures and the hardwired Champion air compressor, and on heavy equipment and rubber tire motor vehicles.
Recent events (1)
- — Z (S) $0
1910.169 B03 I
- Issued
- May 26, 2017
- Abate by
- Jul 14, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.169(b)(3)(i): Compressed air receiver(s) were not equipped with indicating pressure gauge(s) and with one or more spring-loaded safety valves: a) Heavy Mobile Equipment Compressor Room, where the vertical compressed air receiver used in conjunction with the Champion air compressor was not equipped with a pressure gauge and a spring-loaded safety valve.
Recent events (1)
- — Z (S) $0
1910.253 B04 III
- Issued
- May 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: a) Storage Yard, where compressed gas cylinders in storage were not separated: 1. North side of the yard, where four oxygen cylinders and three acetylene cylinders were stored together on one skid. 2. South side of the yard, where two oxygen cylinders and five acetylene cylinders were stored together on one skid.
Recent events (1)
- — Z (S) $0
1910.253 B05 II A
- Issued
- May 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(5)(ii)(A): Valve-protection caps, where cylinder(s) were designed to accept a cap, were not in place: a) North side of the yard, where one oxygen cylinder in storage was not equipped with a valve protection cap.
Recent events (1)
- — Z (S) $0
1910.101 B
- Issued
- May 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: a) Weld Shop, where a compressed gas cylinder containing argon was stored against the wall without being secured. The Bonneville Power Administration was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.101(b), which was contained in OSHA inspection number 979766, citation no. 1, item no. 1, and was affirmed as a final order on September 22, 2014 with respect to a workplace at Ellensburg, WA. The Bonneville Power Administration was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.101(b), which was contained in OSHA inspection number 985644, citation no. 1, item no. 1, and was affirmed as a final order on October 15, 2014 with respect to a workplace at East Wenatchee, WA.
Recent events (1)
- — Z (R) $0
1910.305 G02 III
- Issued
- May 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) Electrician Shop, where the power cord for the Rockwell disc sander, no. 146703, was pulled from the strain relief exposing insulated conductors. The Bonneville Power Administration was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(2)(iii), which was contained in OSHA inspection number 1133722, citation no. 1, item no. 9b, and was affirmed as a final order on July 21, 2016 with respect to a workplace at Vancouver, WA.
Recent events (1)
- — Z (R) $0
1910.1200 F06 II
- Issued
- May 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(6)(ii): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the product identifier and words, pictures, symbols, or combination thereof, which provide at least general information regarding the hazards of the chemicals and which, in conjunction with the other information immediately available to employees under the hazard communication program, would provide employees with the specific information regarding the physical and health hazards of the hazardous chemical: a) Facility, where secondary containers not equipped with labels included: 1. Electrician Shop, spray bottle containing isopropyl alcohol was not equipped with a hazard warning. 2. Substation Supply Shelf, spray bottle containing clear liquid was not labeled.
Recent events (1)
- — Z (O) $0
More inspections at Bonneville Power Administration-Covington District
View Bonneville Power Administration-Covington District's full OSHA safety record →
More inspections in this industry (NAICS 221121)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342296589.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.