COLORADO SPRINGS, CO —
OSHA Inspection: STRESSCON CORPORATION
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of STRESSCON CORPORATION in 3210 ASTROZON BLVD., COLORADO SPRINGS, CO 80935 (NAICS 327390). OSHA activity number 339744039.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STRESSCON CORPORATION
- Site address
- 3210 ASTROZON BLVD.
- City
- COLORADO SPRINGS
- State
- CO
- ZIP
- 80935
- Mailing
- 3210 ASTROZON BLVD., COLORADO SPRINGS, CO 80935
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327390
- Employees
- 165
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.305 G01 IV
- Issued
- Aug 18, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $3,600 · Current $1,800 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)[B]: Flexible cords were run through holes in walls, ceilings, or floors: (a) East batch plant: On or about April 24, 2014, and at times prior, workers were exposed to electrical hazards where a flexible cord passed through a wall opening without a fitting or bushing to prevent damage. Abatement Note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (S) $1800
- — Z (S) $3600
1910.305 B01 I
- Issued
- Aug 18, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: (a) East batch plant: On or about April 24, 2014, and at times prior, workers were exposed to electrical hazards where insulated conductors were exposed to abrasions from a broken conduit fitting at a junction box. Abatement Note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Aug 18, 2014
- Abate by
- Aug 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) Control room: On or about April 24, 2014, and at times prior, workers were exposed to electrical hazards where a small breaker panel had one unused opening. Abatement Note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.110 D10
- Issued
- Aug 18, 2014
- Abate by
- Oct 3, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.110(d)(10): Precautions were not taken to prevent damage to LP gas system(s) from vehicular traffic: (a) East yard: On or about April 24, 2014, and at times prior, workers were exposed to fire hazards where a propane storage tank was located parallel to an employee motor vehicle route without adequate protection from passing vehicles. Abatement Note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.215 A04
- Issued
- Aug 18, 2014
- Abate by
- Oct 3, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: (a) Maintenance building: On or about April 24, 2014, and at times prior, workers were exposed to projectile hazards where a Baldor pedestal grinder work rest was seven-sixteenths inch from the left grinding wheel. Abatement Note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.215 B09
- Issued
- Aug 18, 2014
- Abate by
- Oct 3, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: (a) Maintenance building: On or about April 24, 2014, and at times prior, workers were exposed to projectile hazards where a Baldor pedestal grinder tongue guard 2.25 inches from the left grinding wheel. Abatement Note: Abatement certification is required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Stresscon Corporation
View Stresscon Corporation's full OSHA safety record →
More inspections in this industry (NAICS 327390)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339744039.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.