LOLETA, CA —
OSHA Inspection: BEAR RIVER CASINO HOTEL
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BEAR RIVER CASINO HOTEL in 11 BEAR PAWS WAY, LOLETA, CA 95551 (NAICS 721120). OSHA activity number 339760365.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BEAR RIVER CASINO HOTEL
- Site address
- 11 BEAR PAWS WAY
- City
- LOLETA
- State
- CA
- ZIP
- 95551
- Mailing
- 11 BEAR PAWS WAY, LOLETA, CA 95551
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721120
- Employees
- 250
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.212 A01
- Issued
- Sep 8, 2014
- Abate by
- Sep 25, 2014
- Penalty
- Initial $3,060 · Current $2,295 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: Workshop: On or about May 8, 2014 and at times prior thereto, the drill press did not have a guard at the chuck exposing the maintenance employees to a rotating hazard.
Recent events (2)
- — I (S) $2295
- — Z (S) $3060
1910.212 B
- Issued
- Sep 8, 2014
- Abate by
- Sep 25, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving: Workshop: On or about May 8, 2014 and at times prior thereto, the drill press used to drill wood, steel and plastic pieces was not anchored securely to the floor to prevent walking or moving while operating the equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.215 A04
- Issued
- Sep 8, 2014
- Abate by
- Sep 25, 2014
- Penalty
- Initial $3,060 · Current $2,295 Reduced
General-duty citation text
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: Workshop: On or about May 8, 2014 and at times prior thereto, the Craftsman 6 inch 1/2 HP bench grinder the distance between the abrasive wheel and the work rest measured one quarter of an inch.
Recent events (2)
- — I (S) $2295
- — Z (S) $3060
1910.305 B01 II
- Issued
- Sep 8, 2014
- Abate by
- Sep 25, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Eastside Outside: On or about May 8, 2014 and at times prior thereto, there were knockout openings on the Culter Hammer ETN Safety Switches for Air Purification, condensing units and ice machine unit. b) Mechanical Room: On or about May 8, 2014 and at times prior thereto, there was separation at the elbow from the wall with openings exposing energized wiring leading into the mechanical room.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B02 I
- Issued
- Sep 8, 2014
- Abate by
- Sep 16, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Shop: On or about May 8, 2014 and at times prior thereto, the electrical junction box plate was missing on the south wall. The station was used for charging radios.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 IV A
- Issued
- Sep 8, 2014
- Abate by
- Sep 25, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure; a) Mechanical Room: On or about May 8, 2014 and at times prior thereto, a twenty five foot extension cord was used as fixed wiring for the water heater. The cord was plugged into the outlet which provides water for the bathroom and kitchen. b) Mechanical Room: On or about May 8, 2014 and at times prior thereto, a power strip was suspended and connected to the Culligan water treatment system used as fixed wiring to provide power.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G02 III
- Issued
- Sep 8, 2014
- Abate by
- Sep 25, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) Workshop: On or about May 8, 2014 and at times prior thereto, the flexible cord on Craftsman Dry Vac Model 113 had damaged insulation showing conductor wires at the base of the flexible hose where employees touch the cord. The damaged insulation exposed employees to shock hazards when using as needed for the daily clean up tasks. The vacuum was listed for household use but was used in an industrial setting. b) Workshop: On or about May 8, 2014 and at times prior thereto, the flexible cord on Craftsman Compressor Model 919 had damaged insulation showing conductor wires at the base of the flexible hose where employees touch the cord. The damaged insulation exposed employees to shock hazards when using for the weekly tasks.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.334 A03 II
- Issued
- Sep 8, 2014
- Abate by
- Sep 25, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(3)(ii): Attachment plugs and receptacles were connected or altered in a manner which prevented proper continuity of the electric equipment grounding conductor at the point where plugs were attached to receptacles: Workshop: On or about May 8, 2014 and at times prior thereto, the Genie GS 1930 power cord was missing a grounding prong on the equipment which prevented proper grounding continuity.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Bear River Casino Hotel
View Bear River Casino Hotel's full OSHA safety record →
More inspections in this industry (NAICS 721120)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339760365.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.