Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FORUM ENERGY TECHNOLOGIES

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FORUM ENERGY TECHNOLOGIES in 3110 W. NOBLE AVE, GUTHRIE, OK 73044 (NAICS 332312). OSHA activity number 340113158.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Forum Energy Technologies — free Get an email when a new federal OSHA severe-injury report for Forum Energy Technologies is published. One employer, no account, unsubscribe in one click.
Site address
3110 W. NOBLE AVE
City
GUTHRIE
State
OK
ZIP
73044
Mailing
3110 W. NOBLE AVE, GUTHRIE, OK 73044
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
96
Ownership type
A

2 citations on file for this inspection.

1910.107 C06

Serious Gravity 5 3 instances 4 exposed
Issued
Jan 9, 2015
Abate by
Jan 14, 2015
Penalty
Initial $4,500 · Current $4,500
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not of explosion-proof type approved for Class I, group D locations: and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations.     1)  This violation was observed on or about December 1, 2014, in the paint shop on the south wall, there was a single duplex outlet missing the box cover which was not approved for a Class 1 Division 1 hazardous location exposing employees to the hazards of explosion.      2)  This violation was observed on or about December 1, 2014, in the paint shop on the south wall, an electrical switch box cover to the exhaust fan was cracked with a piece missing which was not approved for a Class 1 Division 1 hazardous location exposing employees to the hazards of  explosion.      3)  This violation observed on or about December 1, 2014, in the paint shop on the south wall on an I-beam a single duplex outlet missing a cover which was not approved for a Class 1 Division 1 hazardous location exposing employees to the hazards of explosion.
Recent events (2)
  • — I (S) $4500
  • — Z (S) $4500

1910.107 G02

Serious Gravity 5 1 instance 6 exposed
Issued
Jan 9, 2015
Abate by
Feb 25, 2015
Penalty
Initial $4,500 · Current $0 Reduced
29 CFR 1910.107(g)(2): All spraying areas were not kept as free from the accumulation of deposits of combustible residues as practical, with cleaning conducted daily if necessary.    This violation was observed on or about December 1, 2014, in the paint shop there was overspray accumulation on such as, but not limited to the floor, walls, piping, conduit, electrical equipment exposing employees to the hazards of fire/explosion.