GUTHRIE, OK —
OSHA Inspection: FORUM ENERGY TECHNOLOGIES
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of FORUM ENERGY TECHNOLOGIES in 3110 W. NOBLE AVE, GUTHRIE, OK 73044 (NAICS 332312). OSHA activity number 340113158.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FORUM ENERGY TECHNOLOGIES
- Site address
- 3110 W. NOBLE AVE
- City
- GUTHRIE
- State
- OK
- ZIP
- 73044
- Mailing
- 3110 W. NOBLE AVE, GUTHRIE, OK 73044
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332312
- Employees
- 96
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.107 C06
- Issued
- Jan 9, 2015
- Abate by
- Jan 14, 2015
- Penalty
- Initial $4,500 · Current $4,500
General-duty citation text
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not of explosion-proof type approved for Class I, group D locations: and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations. 1) This violation was observed on or about December 1, 2014, in the paint shop on the south wall, there was a single duplex outlet missing the box cover which was not approved for a Class 1 Division 1 hazardous location exposing employees to the hazards of explosion. 2) This violation was observed on or about December 1, 2014, in the paint shop on the south wall, an electrical switch box cover to the exhaust fan was cracked with a piece missing which was not approved for a Class 1 Division 1 hazardous location exposing employees to the hazards of explosion. 3) This violation observed on or about December 1, 2014, in the paint shop on the south wall on an I-beam a single duplex outlet missing a cover which was not approved for a Class 1 Division 1 hazardous location exposing employees to the hazards of explosion.
Recent events (2)
- — I (S) $4500
- — Z (S) $4500
1910.107 G02
- Issued
- Jan 9, 2015
- Abate by
- Feb 25, 2015
- Penalty
- Initial $4,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.107(g)(2): All spraying areas were not kept as free from the accumulation of deposits of combustible residues as practical, with cleaning conducted daily if necessary. This violation was observed on or about December 1, 2014, in the paint shop there was overspray accumulation on such as, but not limited to the floor, walls, piping, conduit, electrical equipment exposing employees to the hazards of fire/explosion.
Recent events (2)
- — I (S) $0
- — Z (S) $4500
More inspections at Forum Energy Technologies
View Forum Energy Technologies's full OSHA safety record →
More inspections in this industry (NAICS 332312)
More inspections in OK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340113158.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.