Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: INTERMETRO INDUSTRIES CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of INTERMETRO INDUSTRIES CORPORATION in 1101 N. WASHINGTON ST, WILKES BARRE, PA 18705 (NAICS 332618). OSHA activity number 340421874.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Intermetro Industries Corporation — free Get an email when a new federal OSHA severe-injury report for Intermetro Industries Corporation is published. One employer, no account, unsubscribe in one click.
Site address
1101 N. WASHINGTON ST
City
WILKES BARRE
State
PA
ZIP
18705
Mailing
651 NORTH WASHINGTON STREET, WILKES BARRE, PA 18705
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332618
Employees
200
Ownership type
A

4 citations on file for this inspection.

1910.303 B01

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Jun 5, 2015
Abate by
Jun 25, 2015
Penalty
Initial $4,250 · Current $0 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:  a) Zinc Line, 1101 North Washington Street, Wilkes-Barre, PA - Employees operated, inspected and cleaned around a 480V, 225A rectifier without covers that had exposed energized conductors. Employees were exposed to contact with an electrical current hazard, as observed on or about February 24, 2015.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4250

1910.303 G02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 5, 2015
Abate by
Jun 25, 2015
Penalty
Initial $0 · Current $4,000
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    a) Zinc Line, 1101 North Washington Street, Wilkes-Barre, PA - Employees operated, inspected and cleaned around a 480V, 225A rectifier without covers that had exposed energized conductors. Employees were exposed to contact with an electrical current hazard, as observed on or about February 24, 2015.    In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
  • — I (S) $4000
  • — Z (S) $0

1910.303 G01 I B

Other-than-serious 1 instance 12 exposed
Issued
Jun 5, 2015
Penalty
Initial $3,400 · Current $0 Reduced
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater:    a) STARSYS Department, 1101 North Washington Street, Wilkes-Barre, PA - Employees used, inspected and maintained an energized electrical panel that had an access opening less than thirty-inches (<30") wide due to two (2) metal racking systems located on either side of the electrical panel. The limited access to the electrical panel exposed employees to the hazards associated with being unable to de-energize equipment in the event of an emergency, as observed on or about February 24, 2015.    In accordance with 29 CFR 1903.19(c), abatement certification is not required for this violation. The hazardous condition was corrected during the inspection.
Recent events (2)
  • — I (O) $0
  • — Z (S) $3400

1910.303 G01 II

Deleted Serious Gravity 5 1 instance 12 exposed
Issued
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less was used for storage:  a) STARSYS Department, 1101 North Washington Street, Wilkes-Barre, PA - Employees used, inspected and maintained an energized electrical panel that had two (2) metal racking storage systems, a garbage pail, and two (2) brooms stored within the working space of the electrical panel. The limited access to the electrical panel exposed employees to the hazards associated with being unable to de-energize equipment in the event of an emergency, as observed on or about February 24, 2015.  In accordance with 29 CFR 1903.19(c), abatement certification is not required for this violation. The hazardous condition was corrected during the inspection.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Intermetro Industries Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340421874.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.