TAMUNING, GU —
OSHA Inspection: LEADING TECH CONSTRUCTION CO.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LEADING TECH CONSTRUCTION CO. in PIA MARINE HOTEL 193 TUMON LANE, TAMUNING, GU 96913 (NAICS 236220). OSHA activity number 340568005.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LEADING TECH CONSTRUCTION CO.
- Site address
- PIA MARINE HOTEL 193 TUMON LANE
- City
- TAMUNING
- State
- GU
- ZIP
- 96913
- Mailing
- PO BOX 315839, TAMUNING, GU 96931
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 3
- Ownership type
- A
Citations
6 citations on file for this inspection.
1926.404 B01 I
- Issued
- Sep 14, 2015
- Abate by
- Sep 21, 2015
- Penalty
- Initial $1,200 · Current $1,200
General-duty citation text
29 CFR 1926.404(b)(1)(i): General. The employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors. (a) At the Pia Marine Hotel project, the employer failed to provide ground fault circuit interrupters for employee that used Ridgid cut off saw and Makita square sander inside a building. The tools were connected to a wall outlet receptacle missing a cover face. Employees were exposed to the hazards of electrical shock.
Recent events (1)
- — Z (S) $1200
1926.405 B01
- Issued
- Sep 14, 2015
- Abate by
- Sep 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not also effectively closed: (a) At the Pia Marine Hotel project, one 110 VAC wall outlet receptacle box was not provided with a face cover plate and the exposed terminals were energized. The box was located less than 24 inches above the walking and working floor. Employees were exposed to possible accidental contact with exposed live parts and receive an electrical burn and shock.
Recent events (1)
- — Z (S) $0
1926.405 G02 IV
- Issued
- Sep 14, 2015
- Abate by
- Sep 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Strain relief. Flexible cords were not connected to devices and fittings so that strain relief was provided which will prevent pull from being directly transmitted to joints or terminal screws. (a) At the Pia Marine Hotel project, the outside insulation on an extension cord was not connected to the plug that was used to power two portable Ridgid cut off saw and Makita square sander, exposing employees to the hazard of contacting live electrical wires.
Recent events (1)
- — Z (S) $0
1926.25 A
- Issued
- Sep 14, 2015
- Abate by
- Sep 21, 2015
- Penalty
- Initial $1,200 · Current $1,200
General-duty citation text
29 CFR 1926.25(a): During the course of construction, alteration, or repairs, form and scrap lumber with protruding nails, and all other debris, were not kept cleared from work areas, passageways, and stairs, in and around buildings or other structures: (a) At the Pia Marine Hotel project, lumber with protruding nails and other debris were not removed from walking and working surface inside the project site. Employees were exposed to stepping on the nails.
Recent events (1)
- — Z (S) $1200
1926.50 D01
- Issued
- Sep 14, 2015
- Abate by
- Oct 8, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.50(d)(1): First aid supplies were not easily accessible when required: (a) At the Pia Marine Hotel project, there were no first aid supplies onsite. Employees used Ridgid cut off saw and Makita sander at the project.
Recent events (1)
- — Z (O) $0
1926.404 F06
- Issued
- Sep 14, 2015
- Abate by
- Sep 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, and enclosures was not permanent and continuous: (a) At the Pia Marine Hotel project, there was no grounding prong on the extension cord that powered a 110 VAC Ridgid cut off saw and Makita square sander. The tools were powered through an extension cord missing the prong. The cord was plugged into an interior outlet. Employee was exposed to the hazards of electrical shock.
Recent events (1)
- — Z (O) $0
More inspections at Leading Tech Construction CO.
View Leading Tech Construction CO.'s full OSHA safety record →
More inspections in this industry (NAICS 236220)
More inspections in GU
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340568005.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.