CHINO VALLEY, AZ —
OSHA Inspection: U.S. FOREST SERVICE-PRESCOTT NATIONAL FOREST
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of U.S. FOREST SERVICE-PRESCOTT NATIONAL FOREST in CHINO VALLEY RANGER DISTRICT 735 NORTH HWY. 89, CHINO VALLEY, AZ 86323 (NAICS 924120). OSHA activity number 340616549.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. FOREST SERVICE-PRESCOTT NATIONAL FOREST
- Site address
- CHINO VALLEY RANGER DISTRICT 735 NORTH HWY. 89
- City
- CHINO VALLEY
- State
- AZ
- ZIP
- 86323
- Mailing
- 2971 WILLOW CREEK ROAD, BLDG. 4, PRESCOTT, AZ 86301
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 10
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.106 D02 I
- Issued
- Oct 22, 2015
- Abate by
- Nov 18, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(2)(i): Approved containers and/or portable tanks were not used for the storage of flammable liquids: (a) Chino Valley Ranger District, outside flammable storage cabinet: On or about May 7, 2015 and at times prior thereto, gasoline was stored in two dolmar-style containers. These two-compartment fuel/oil propylene containers, which comply with standard specification ASTM F 852, are not approved under the Nationally Recognized Testing Laboratory (NRTL) program since ASTM F 852 is not a recognized test standard under the NRTL program. In addition, the storage area was not provided with a fire detection system capable of detecting incipient stage fires.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Oct 22, 2015
- Abate by
- Nov 18, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Chino Valley Ranger District, bullpen: On or about May 7, 2015 and at times prior thereto, a relocatable power tap was used to power a high current draw heater (1320 watts).
Recent events (1)
- — Z (S) $0
1910.303 G01
- Issued
- Oct 22, 2015
- Abate by
- Nov 18, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) Chino Valley Ranger District, storage room-janitor's closet: On or about May 7, 2015 and at times prior thereto, two electrical breaker panels (A & B) were blocked by a hand truck, shovel and janitorial supplies.
Recent events (1)
- — Z (S) $0
1910.305 J02 IV
- Issued
- Oct 22, 2015
- Abate by
- Nov 18, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: (a) Chino Valley Ranger District, snack area: On or about May 7, 2015 and at times prior thereto, the receptacle in the sink area did not have ground fault protection.
Recent events (1)
- — Z (S) $0
1910.37 B01
- Issued
- Oct 22, 2015
- Abate by
- Nov 18, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that employees with normal vision could see along the exit route: a) Chino Valley Ranger District, bullpen hallway: On or about May 7, 2015 and at times prior thereto, the emergency light did not work.
Recent events (1)
- — Z (O) $0
More inspections at U.S. Forest Service-Prescott National Forest
View U.S. Forest Service-Prescott National Forest's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in AZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340616549.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.