Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FOREST SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FOREST SERVICE in P.O. BOX 280, CORDOVA, AK 99574 (NAICS 924120). OSHA activity number 340696160.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Forest Service — free Get an email when a new federal OSHA severe-injury report for Forest Service is published. One employer, no account, unsubscribe in one click.
Establishment
FOREST SERVICE
Site address
P.O. BOX 280
City
CORDOVA
State
AK
ZIP
99574
Mailing
P.O. BOX 280, CORDOVA, AK 99574
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
35
Ownership type
D

9 citations on file for this inspection.

1910.23 A02

Serious Gravity 10 1 instance 3 exposed
Issued
Jun 24, 2015
Abate by
Jul 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.23(a)(2): Ladderway floor opening(s) or platform(s) were not guarded by a standard railing with standard toeboard(s) on all exposed sides (except at the entrance to opening) with passage through the railing either provided with a swinging gate or so offset that a person could walk directly into the opening.  Boat house; on or about 09 June 2015 and times prior thereto; fall protection was not provided between the boat house and the gangway connection. An opening of approximately 30 inches in width; with a height of approximately 15 feet over the water was not guarded. This condition exposed employees to a fall hazard.
Recent events (1)
  • — Z (S) $0

1910.37 A04

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 24, 2015
Abate by
Jul 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times.   New bunkhouse, boiler room; on or about 09 June 2015 and times prior thereto; emergency exit lights were inoperative.  Emergency light was damaged. This condition exposed employees to delays in exiting the building and smoke inhalation, fire, and tripping hazards.
Recent events (1)
  • — Z (S) $0

1910.37 B01

Serious Gravity 1 2 instances 12 exposed
Issued
Jun 24, 2015
Abate by
Jul 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(1): The exit route was not adequately lit so that an employee with normal vision could see along the exit route.   Four-plex entryway; on or about 09 June 2015 and times prior thereto; emergency lighting was not available along the exit route. This condition exposed employees to delays in exiting the building and smoke inhalation, fire, and tripping hazards.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 1 2 instances 12 exposed
Issued
Jun 24, 2015
Abate by
Jul 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit".  New bunkhouse, west end and four-plex entryway; on or about 09 June 2015 and times prior thereto; two instances were noted where exits were not posted along the exit route:        (a) New bunkhouse west end, adjacent to latrines, exit route was not marked with an exit sign.        (b) Four-plex entryway, exit route was not marked with an exit sign.  This condition exposed employees to delays in exiting the building and smoke inhalation, fire, and tripping hazards.
Recent events (1)
  • — Z (S) $0

1910.215 A04

Serious Gravity 1 1 instance 10 exposed
Issued
Jun 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch.   Warehouse, work bench area; on or about 09 June 2015 and times prior thereto; the work rest on a Dayton 6 inch bench grinder, model number 4Z123G, lot number 200107 was not properly adjusted to a maximum of 1/8 of an inch from the abrasive wheel. The gap between the abrasive wheel and work rest measured approximately 1/4 of an inch. This condition exposed employees to a caught in hazard.
Recent events (1)
  • — Z (S) $0

1910.303 G02 II

Serious Gravity 1 2 instances 10 exposed
Issued
Jun 24, 2015
Abate by
Jul 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage.  Four-plex housing unit; on or about 09 June 2015 and times prior thereto; , two wall mounted light fixtures located 73 inches from the floor had exposed bulbs that were not protected. This condition exposed employees to an electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.304 F01 IV

Serious Gravity 1 1 instance 4 exposed
Issued
Jun 24, 2015
Abate by
Jul 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel.   Old bunkhouse, kitchen area; on or about 09 June 2015 and times prior thereto; the employer did not ensure that the electrical panels were readily accessible. A microwave oven and a countertop were placed in front of the electrical panel impeding immediate access.  This condition exposed employees to an electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 2 instances 1 exposed
Issued
Jun 24, 2015
Abate by
Jul 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  Warehouse, Boiler room; on or about 09 June 2015 and times prior thereto; knockout plugs were missing on two energized electrical boxes that supplies power to the boiler control shutoff switches. This condition exposed employees to an electrical shock and electrical burn hazards.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 3 exposed
Issued
Jun 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  Warehouse, Fish Cache; on or about 09 June 2015 and times prior thereto; a 25 foot extension cord was used as a substitute for permanent wring. This condition exposed employees to electrical shock and electrical burn hazard.
Recent events (1)
  • — Z (S) $0

View Forest Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340696160.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.