YARDLEY, PA —
OSHA Inspection: PENNSYLVANIA AMERICAN WATER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PENNSYLVANIA AMERICAN WATER in 1145 EDGEWOOD RD, YARDLEY, PA 19067 (NAICS 221310). OSHA activity number 340794601.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PENNSYLVANIA AMERICAN WATER
- Site address
- 1145 EDGEWOOD RD
- City
- YARDLEY
- State
- PA
- ZIP
- 19067
- Mailing
- 800 WEST HERSHEYPARK DRIVE, HERSHEY, PA 17033
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221310
- Employees
- 15
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.119 L02
- Issued
- Oct 27, 2015
- Abate by
- Nov 4, 2015
- Penalty
- Initial $3,825 · Current $1,913 Reduced
General-duty citation text
29 CFR 1910.119(l)(2): Management of change procedures did not assure that the considerations required by (l)(2)(1) through (l)(2)(v) were addressed prior to any change. a) Yardley Plant, chlorine system - On or about July 22, 2015, it was determined the employer had not implemented the procedures to manage change prior to addition of a Halogen valve system that had a start up date of January 28, 2015.
Recent events (3)
- — F (S) $1912.5
- — C (S) $3825
- — Z (S) $3825
1910.119 L04
- Issued
- Oct 27, 2015
- Abate by
- Nov 4, 2015
- Penalty
- Initial $3,825 · Current $1,913 Reduced
General-duty citation text
29 CFR 1910.119(l)(4): Process safety information required by paragraph (d) of this section was not updated when a change covered by this paragraph resulted in a change in the process safety information. a) Yardley Plant, chlorine system - On or about July 22, 2015, Piping and instrument diagrams (P&ID's) were not updated after the addition of a Halogen valve system; the change is covered under this paragraph and had a start up date of January 28, 2015.
Recent events (3)
- — F (S) $1912.5
- — C (S) $3825
- — Z (S) $3825
1910.119 D02 I A
- Issued
- Oct 27, 2015
- Abate by
- Nov 4, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(d)(2)(i)(A): The employer did not include a block flow diagram or simplified process flow diagram as part of process safety information concerning technology of the process. a) Yardley water plant - On or about July 22,2015, the employers Process Safety Information (PSI) did not include a block flow diagram or simplified process flow diagram.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Pennsylvania American Water
View Pennsylvania American Water's full OSHA safety record →
More inspections in this industry (NAICS 221310)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340794601.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.