OSHA Inspection: COOK BROTHERS BUILDING & EXCAVATING, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of COOK BROTHERS BUILDING & EXCAVATING, INC. in BROOKHAVEN ROAD & PLEASANTHILL ROAD, MORGANTOWN, WV 26501 (NAICS 238160). OSHA activity number 340970664.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Cook Brothers Building & Excavating, INC. — free Get an email when a new federal OSHA severe-injury report for Cook Brothers Building & Excavating, INC. is published. One employer, no account, unsubscribe in one click.
Site address
BROOKHAVEN ROAD & PLEASANTHILL ROAD
City
MORGANTOWN
State
WV
ZIP
26501
Mailing
4006 FREEDOM HIGHWAY SUITE 1, FAIRMONT, WV 26554
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238160
Employees
11
Ownership type
A

7 citations on file for this inspection.

1926.150 C01 IV

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 22, 2015
Abate by
Jan 20, 2016
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1926.150(c)(1)(iv): One or more fire extinguishers, rated not less than 2A, were not provided on each floor:     a.)  Cook Brothers Building & Excavating, Inc., Morgantown, WV:  On or about 10/07/15, a fire extinguisher was not provided for each floor of the townhome apartment complex being built.     ABATEMENT CERTIFICATION IS REQUIRED.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1926.405 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 22, 2015
Abate by
Jan 20, 2016
Penalty
Initial $2,400 · Current $1,200 Reduced
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:      a.)  Cook Brothers Building & Excavating, Inc., Morgantown, WV:  On or about 10/07/15, the unused circuit breaker openings in the temporary power panel were not effectively closed.      ABATEMENT CERTIFICATION IS REQUIRED.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2400

1926.403 I02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 22, 2015
Abate by
Jan 20, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.   a.)  Cook Brothers Building & Excavating, Inc., Morgantown, WV:  On or about 10/07/15, the live 120 volt bus bar for the temporary power panel was not guarded to prevent accidental contact by an employee.   ABATEMENT CERTIFICATION IS REQUIRED.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.1052 C01 II

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 22, 2015
Abate by
Jan 20, 2016
Penalty
Initial $2,400 · Current $1,200 Reduced
29 CFR 1926.1052(c)(1)(ii): Stairways having four or more risers or rising more than 30 inches (76 cm), whichever is less, were not equipped with a stairrail system along each unprotected side or edge:     a.)  Cook Brothers Building & Excavating, Inc., Morgantown, WV:  On or about 10/07/15, a stairrail system was not provided for the 5 risers of the stair way built for access to the second story of the apartment building.     ABATEMENT CERTIFICATION IS REQUIRED.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2400

1926.404 B01 II

Repeat Gravity 5 1 instance 10 exposed
Issued
Dec 22, 2015
Abate by
Jan 20, 2016
Penalty
Initial $3,200 · Current $1,600 Reduced
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection.     a.)  Cook Brothers Building & Excavating, Inc., Morgantown, WV:  On or about 10/07/15, the temporary receptacle box providing power to the Dewalt air compressors, Dewalt circular saws, and extension cords had ground fault circuit interrupters that were broken and not protecting employees.     Cook Brothers Building & Excavating, Inc., was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1926.404(b)(1)(ii), which was contained in OSHA inspection number 594258, Citation 01, Item number 005 and was affirmed as final order on 02/07/13, with respect to a workplace located at South Pike Street, Shinnston, WV 26431.     ABATEMENT CERTIFICATION AND DOCUMENTATION IS REQUIRED.
Recent events (2)
  • — I (R) $1600
  • — Z (R) $3200

1926.404 F06

Repeat Gravity 5 1 instance 10 exposed
Issued
Dec 22, 2015
Abate by
Jan 20, 2016
Penalty
Initial $3,200 · Current $1,600 Reduced
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:     a.)  Cook Brothers Building & Excavating, Inc., Morgantown, WV:  On or about 10/07/15, three of the four energized temporary power receptacles providing power to a Dewalt air compressor, extension cords, and Dewalt circular saws were showing an open ground.        Cook Brothers Building & Excavating, Inc., was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1926.404(f)(6), which was contained in OSHA inspection number 594258, Citation 01, Item number 004b and was affirmed as final order on 02/07/13, with respect to a workplace located at South Pike Street, Shinnston, WV 26431.     ABATEMENT CERTIFICATION AND DOCUMENTATION IS REQUIRED.
Recent events (2)
  • — I (R) $1600
  • — Z (R) $3200

1926.501 B13

Repeat Gravity 5 1 instance 2 exposed
Issued
Dec 22, 2015
Abate by
Jan 20, 2016
Penalty
Initial $4,000 · Current $2,000 Reduced
29 CFR 1926.501(b)(13): Each employee(s) engaged in residential construction activities 6 feet (1.8 m) or more above lower levels were not protected by guardrail systems, safety net system, or personal fall arrest system, nor were employee(s) provided with an alternative fall protection measure under another provision of paragraph 1926.501 (b):      a.)  Cook Brothers Building & Excavating, Inc., Morgantown, WV:  On or about 10/07/15, two employees were working on the roof of a newly built apartment home with a 5/12 slope approximately 26' above the ground without the use of fall protection.     ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
  • — I (R) $2000
  • — Z (R) $4000

View Cook Brothers Building & Excavating, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340970664.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.