HAVILAND, OH —
OSHA Inspection: HAVILAND PLASTIC PRODUCTS, CO.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of HAVILAND PLASTIC PRODUCTS, CO. in 119 MAIN ST., HAVILAND, OH 45851 (NAICS 326199). OSHA activity number 341003028.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HAVILAND PLASTIC PRODUCTS, CO.
- Site address
- 119 MAIN ST.
- City
- HAVILAND
- State
- OH
- ZIP
- 45851
- Mailing
- P.O. BOX 38, HAVILAND, OH 45851
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 60
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 B01 II
- Issued
- Feb 2, 2016
- Abate by
- Feb 11, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.303(b)(1)(ii): Electric equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees. The safety of equipment was not determined by considering the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, and the adequacy of the protection thus provided. a. Haviland Plastic Products, Co. located in Haviland, Ohio: On or about October 19, 2015, the employer did not ensure wire nuts used to splice 480 volt conductors for the heater bands on plastic blow molding press #18, located in the production department, were enclosed in an approved box at each splice point. Abatement Note: One feasible and acceptable method to correct this hazard is to comply with National Fire Protection Association (NFPA) Standard 70, National Electric Code 2014 Ed. - Section 300, and or comply with Tempco Electric Heater Corporation engineering data specification that states all wiring needs to comply with the National Electrical Code.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.303 G02 I
- Issued
- Feb 2, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures. a. Haviland Plastic Products, Co. located in Haviland, Ohio: On or about October 19, 2015, junction boxes for the heater band electrical supply conductors on plastic blow molding press #18, located in the production department, were not equipped with covers, exposing employees to accidental contact with the energized conductor terminals.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.332 B01
- Issued
- Feb 2, 2016
- Abate by
- Mar 31, 2016
- Penalty
- Initial $5,390 · Current $5,390
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments. a. Haviland Plastic Products, Co. located in Haviland, Ohio: On or about September 26, 2015, an employee was not properly trained on electrical protective equipment to be worn and electrical shock hazards prior to being exposed to energized electrical equipment when reaching into the 480 volt electrical panel for plastic blow molding press #18 to activate a reset switch. b. Haviland Plastic Products, Co. located in Haviland, Ohio: On or about October 5, 2015, an employee was not properly trained on the proper electrical protective equipment to be worn and proper inspection of electrical testing equipment prior to troubleshooting a contactor inside of the 480 volt electrical panel for plastic blow molding press #1.
Recent events (2)
- — I (S) $5390
- — Z (S) $5390
1910.333 A
- Issued
- Feb 2, 2016
- Abate by
- Feb 11, 2016
- Penalty
- Initial $5,390 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices were not consistent with the nature and extent of the associated electrical hazards. a. Haviland Plastic Products, Co. located in Haviland, Ohio: On or about October 5, 2015, the employer did not ensure an employee locked out the electrical power prior to re-wiring a contactor inside of the 480 volt electrical panel for plastic blow molding press #1.
Recent events (2)
- — I (S) $0
- — Z (S) $5390
1910.333 B02 I
- Issued
- Feb 2, 2016
- Abate by
- Mar 4, 2016
- Penalty
- Initial $5,390 · Current $4,305 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives. a. Haviland Plastic Products, Co. located in Haviland, Ohio: On or about September 26, 2015, the employer did not ensure procedures were developed to safely lockout electrical equipment.
Recent events (2)
- — I (S) $4305
- — Z (S) $5390
1910.335 A01 I
- Issued
- Feb 2, 2016
- Abate by
- Feb 11, 2016
- Penalty
- Initial $5,390 · Current $4,305 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed. a. Haviland Plastic Products, Co. located in Haviland, Ohio: On or about September 26, 2015, an employee was not wearing electrical protective equipment for the hands, face, head, and body when exposed to live electrical equipment when reaching into the 480 volt electrical panel for plastic blow molding press #18 to activate a reset switch.
Recent events (2)
- — I (S) $4305
- — Z (S) $5390
More inspections at Haviland Plastic Products, CO.
View Haviland Plastic Products, CO.'s full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341003028.