Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. GEOLOGICAL SURVEY - FIELD SERVICE FACILITY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. GEOLOGICAL SURVEY - FIELD SERVICE FACILITY in 8914 LAKEVIEW AVENUE SW, LAKEWOOD, WA 98499 (NAICS 924110). OSHA activity number 341201242.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Geological Survey - Field Service Facility — free Get an email when a new federal OSHA severe-injury report for U.S. Geological Survey - Field Service Facility is published. One employer, no account, unsubscribe in one click.
Site address
8914 LAKEVIEW AVENUE SW
City
LAKEWOOD
State
WA
ZIP
98499
Mailing
934 BROADWAY, SUITE 300, TACOMA, WA 98402
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924110
Employees
2
Ownership type
D

9 citations on file for this inspection.

1910.22 D01

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate:   a)       Metal Shop;  Cable car equipment was stored on an overhead storage area with no load rating.
Recent events (1)
  • — Z (S) $0

1910.23 E02

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.23(e)(2): Stair rails did not consist of a top rail, intermediate rail and/or posts, with the vertical height not more than 34 inches (86.36 cm) nor less than 30 inches (76.2 cm) from upper surface of top rail to surface of tread in line with face of riser at forward edge of tread:  a)       Records Storage Area Main Shop;  The staircase did not have a midrail, exposing employees to potential fall hazards.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 1 2 instances 2 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  a)      Wood Shop;  The exit discharge door did not have an EXIT sign.   b)      South End of Main Shop;  The exit discharge door did not have an EXIT sign.
Recent events (1)
  • — Z (S) $0

1910.37 B04

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:  a)  Field Services Room, Main Shop;  Directional signs were not posted which indicated direction of travel to exit building.
Recent events (1)
  • — Z (S) $0

1910.37 B06

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:   a)       The EXIT sign in the metal shop was not illuminated.
Recent events (1)
  • — Z (S) $0

1910.212 B

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.212(b): Anchoring fixed machinery. Machines designed for a fixed location shall be securely anchored to prevent walking or moving:  a)       Metal Shop;  The Grizzly drill press was not bolted to the floor.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   a)      South End of Main Shop;  Office relocatable power taps were attached to the wall and used in a dirty and corrosive environment.  The UL listing and labeling states that this type of relocatable power tap is for office environments only, not shop environments which can be dirty, oily, or corrosive.  The UL listing and labeling also states that relocatable power taps are not designed to be attached to a surface. This exposes employees to possible electrical fire hazards.
Recent events (1)
  • — Z (S) $0

1910.157 E03

Other-than-serious 1 instance 1 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  Note:  Applies to any extinguishers provided in the workplace.  Maintenance check includes an internal examination, except extinguishers with stored pressure.   a)       FSU Storage Room;  Two Amerex fire extinguishers did not have an annual check since March 2014.
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 2 instances 2 exposed
Issued
Feb 3, 2016
Abate by
Mar 9, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a)      Field Services Room, Main Shop;  A metal box which contained hornets monitoring equipment was stored underneath the breaker panel.   b)      FSU Storage Room;  A plastic box was stored underneath the breaker panel.    This exposes employees to possible tripping and struck by hazards.
Recent events (1)
  • — Z (O) $0

View U.S. Geological Survey - Field Service Facility's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341201242.