WHEELING, IL —
OSHA Inspection: THE PENRAY COMPANIES, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of THE PENRAY COMPANIES, INC. in 440 DENNISTON COURT, WHEELING, IL 60090 (NAICS 325998). OSHA activity number 341258929.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE PENRAY COMPANIES, INC.
- Site address
- 440 DENNISTON COURT
- City
- WHEELING
- State
- IL
- ZIP
- 60090
- Mailing
- 440 DENNISTON COURT, WHEELING, IL 60090
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325998
- Employees
- 68
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.106 B04 II
- Issued
- Jun 17, 2016
- Abate by
- Jun 23, 2016
- Penalty
- Initial $4,200 · Current $1,200 Reduced
00401371
General-duty citation text
29 CFR 1910.106(b)(4)(ii): Vents for tanks inside buildings were not as provided in subparagraphs (2)(iv), (v), (vi)(b), and (3)(iv) of this paragraph: The Penray Companies, Inc. did not ensure that the aboveground storage tanks had some form of device that relieved excessive internal pressure caused by exposure fires. (A) On February 18, 2016, the emergency relief vent on the atmospheric storage tank V-6, containing heptane, located in the blending room, was not replaced once activated but instead the break links was replaced with a wire. (B) On February 18, 2016 the emergency relief vent on the atmospheric storage tank V-7, containing acetone, located in the blending room, was not replaced once activated instead the the break link was replaced with a nail.
Recent events (2)
- — I (O) $1200
- — Z (S) $4200
More inspections at The Penray Companies, INC.