OSHA Inspection: THE PENRAY COMPANIES, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of THE PENRAY COMPANIES, INC. in 440 DENNISTON COURT, WHEELING, IL 60090 (NAICS 325998). OSHA activity number 341258929.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Penray Companies, INC. — free Get an email when a new federal OSHA severe-injury report for The Penray Companies, INC. is published. One employer, no account, unsubscribe in one click.
Site address
440 DENNISTON COURT
City
WHEELING
State
IL
ZIP
60090
Mailing
440 DENNISTON COURT, WHEELING, IL 60090
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325998
Employees
68
Ownership type
A

1 citation on file for this inspection.

1910.106 B04 II

Other-than-serious 2 instances 2 exposed
Issued
Jun 17, 2016
Abate by
Jun 23, 2016
Penalty
Initial $4,200 · Current $1,200 Reduced

Hazardous substances 00401371

29 CFR 1910.106(b)(4)(ii): Vents for tanks inside buildings were not as provided in subparagraphs (2)(iv), (v), (vi)(b), and (3)(iv) of this paragraph:    The Penray Companies, Inc. did not ensure that the aboveground storage tanks had some form of device that relieved excessive internal pressure caused by exposure fires.     (A) On February 18, 2016, the emergency relief vent on the atmospheric storage tank V-6, containing heptane, located in the blending room, was not replaced once activated but instead the break links was replaced with a wire.     (B) On February 18, 2016 the emergency relief vent on the atmospheric storage tank V-7, containing acetone, located in the blending room, was not replaced once activated instead the the break link was replaced with a nail.
Recent events (2)
  • — I (O) $1200
  • — Z (S) $4200

View The Penray Companies, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341258929.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.