ORANGE PARK, FL —
OSHA Inspection: STONE HOUSE ENTERPRISES, INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of STONE HOUSE ENTERPRISES, INC. in 124 INDUSTRIAL LOOP W, ORANGE PARK, FL 32073 (NAICS 327991). OSHA activity number 341306652.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STONE HOUSE ENTERPRISES, INC.
- Site address
- 124 INDUSTRIAL LOOP W
- City
- ORANGE PARK
- State
- FL
- ZIP
- 32073
- Mailing
- 124 INDUSTRIAL LOOP W, ORANGE PARK, FL 32073
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327991
- Employees
- 23
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.110 F02 I
- Issued
- Jun 29, 2016
- Penalty
- Initial $2,000 · Current $2,000
General-duty citation text
29 CFR 1910.110(f)(2)(i): Containers in storage were not located so as to minimize exposure to excessive temperature rise, physical damage, or tampering from unauthorized persons: a. On or about March 8, 2016, inside the shop area, (3) large LP gas tanks and (3) small LP gas tanks were not stored in a manner that would minimize exposure to physical damage in that they were left in close proximity to forklift traffic.
Recent events (2)
- — I (S) $2000
- — Z (S) $2000
1910.147 C01
- Issued
- Jun 29, 2016
- Abate by
- Jul 26, 2016
- Penalty
- Initial $1,200 · Current $800 Reduced
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: a. On or about March 8, 2016, the employer did not have a written Lockout/Tagout program that consisted of written specific instructions on how to lockout equipment in the shop such as the ZDCQ bridge cutting machine and the compressor located behind the building when performing servicing or maintenance on such equipment, employee training and periodic inspections.
Recent events (2)
- — I (S) $800
- — Z (S) $1200
1910.219 D01
- Issued
- Jun 29, 2016
- Penalty
- Initial $1,200 · Current $0 Reduced
General-duty citation text
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): a. On or about March 8, 2016, back yard area, the air compressor belt did not have a guard and exposed employees to the belt.
Recent events (2)
- — I (S) $0
- — Z (S) $1200
1910.303 G01 II
- Issued
- Jun 29, 2016
- Penalty
- Initial $1,200 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a. On or about March 8, 2016, shop area, items such as but not limited to (5) man-made granite slabs were stored within 3 feet of the electrical box.
Recent events (2)
- — I (O) $0
- — Z (S) $1200
1910.305 B01 II
- Issued
- Jun 29, 2016
- Abate by
- Jul 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a. On or about March 8, 2016, unused openings in the electrical panel located near the bay door had missing blanks.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.37 B02
- Issued
- Jun 29, 2016
- Abate by
- Jul 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit must be clearly visible and marked by a sign reading "Exit." a. On or about March 8, 2016, all exits were not marked by a sign reading "Exit".
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 C01
- Issued
- Jun 29, 2016
- Abate by
- Jul 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a. On or about March 8, 2016, a fire extinguisher located near the front roll-up door was not mounted, located nor identified so that it was readily accessible.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 G01
- Issued
- Jun 29, 2016
- Abate by
- Jul 12, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting: a. On or about March 8, 2016, employees required to put out fires had not received fire extinguisher training.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.178 L01 II
- Issued
- Jun 29, 2016
- Abate by
- Jul 26, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(1)(ii): The employer did not ensure that each operator had successfully completed the training required by paragraph (l), except as permitted by paragraph (l)(5), prior to permitting an employee to operate a forklift: a. On or about March 8, 2016, the employer did not ensure that employees operating forklifts to move granite pieces and load and/or unload trucks were trained prior to the employees operating the lifts.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Stone House Enterprises, INC.
View Stone House Enterprises, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 327991)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341306652.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.