Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: VIGOR ALASKA SEWARD, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of VIGOR ALASKA SEWARD, LLC in MILE 7 NASH ROAD, SEWARD, AK 99664 (NAICS 336611). OSHA activity number 341382059.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Vigor Alaska Seward, LLC for free Get an email when a new federal OSHA severe-injury report for Vigor Alaska Seward, LLC is published. One employer, no account, unsubscribe in one click.
Site address
MILE 7 NASH ROAD
City
SEWARD
State
AK
ZIP
99664
Mailing
MILE 7 NASH ROAD, SEWARD, AK 99664
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336611
Employees
40
Ownership type
Private (A)

10 citations on file for this inspection.

1910.242 B

Serious Gravity 1 1 instance 3 exposed
Issued
May 10, 2016
Penalty
Initial $2,550 · Current $1,785 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.  Machine shop:  On or about 6 October 2015 and times prior thereto, an air nozzle did not have 30 P.S.I reducing device.  This exposed employees to air embolism/laceration hazards if they contacted the discharge to their skin.
Recent events (2)
  • · I (S) $1785
  • · Z (S) $2550

1910.303 F02

Serious Gravity 1 2 instances 3 exposed
Issued
May 10, 2016
Abate by
Jun 8, 2016
Penalty
Initial $2,550 · Current $1,785 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.   (a) Generator/Air compressor Bldg:  On or about 6 April 2016 and times prior thereto, the electrical panel P-227 was not properly identified with a listing for the circuits.  This condition exposed employees to an electrical shock and burn hazard.    (b) Docking Shack:  On or about 6 April 2016 and times prior thereto, the electrical panel (number unknown) was not properly identified with a listing for the circuits.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
  • · I (S) $1785
  • · Z (S) $2550

1910.303 G01

Serious Gravity 1 1 instance 3 exposed
Issued
May 10, 2016
Abate by
Jun 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment.  Machine Shop, Latrine Closet:  On or about 6 April 2016 and times prior thereto, a 480 volt electrical circuit breaker panel was not accessible to employees.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 G02 I

Serious Gravity 1 2 instances 5 exposed
Issued
May 10, 2016
Abate by
Jun 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures.  Machine shop:  On or about 6 April 2016 and times prior thereto, the 480 volt Bus ducts had four locally fabricated wooden end caps installed and duct taped into place.  This condition exposed employees to a fire hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.304 G05

Serious Gravity 1 16 instances 5 exposed
Issued
May 10, 2016
Penalty
Initial $2,550 · Current $1,785 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.   Coating Shop:  On or about 6 April 2016 and times prior thereto, the electrical circuit consisting of 16 electrical outlets were not connected to a ground circuit. This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
  • · I (S) $1785
  • · Z (S) $2550

1910.305 B01 II

Serious Gravity 1 2 instances 7 exposed
Issued
May 10, 2016
Abate by
Jun 8, 2016
Penalty
Initial $2,550 · Current $1,785 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed  (a) Machine shop/tooling area:  On or about 6 April 2016 and times prior thereto; A knockout plug was missing from a energized electrical outlet box. This condition exposed employees to electrical shock and electrical burn hazard.   (b) Bldg 804/Electrical:  On or about 6 April 2016 and times prior thereto; A knockout plug was missing from the energized entrance light switch. This condition exposed employees to electrical shock and electrical burn hazard.
Recent events (2)
  • · I (S) $1785
  • · Z (S) $2550

1910.305 J01 I

Serious Gravity 1 2 instances 5 exposed
Issued
May 10, 2016
Abate by
Jun 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located had live parts normally exposed to employee contact.  (a) QA Room:  On or about 6 April 2016 and times prior thereto, a 120 electrical outlet cover was missing on the south wall of the room.  This condition exposed employees to an electrical shock and burn hazard.  (b) Services Conex:  On or about 6 April 2016 and times prior thereto, a 120 electrical outlet cover was missing on the conex.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 J02 VI

Serious Gravity 1 1 instance 3 exposed
Issued
May 10, 2016
Abate by
Jun 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(vi): A receptacle installed in a wet location where the product intended to be plugged into it was not to be attended while in use (for example, sprinkler system controllers, landscape lighting, and holiday lights) did not have an enclosure that was weatherproof with the attachment plug cap inserted   Old Tool room Building, back side:  On Or About 6 April 2016 and times prior thereto, an electrical outlet was missing the waterproof cover.  This condition exposed employees to an electrical shock hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1915.89 B

Serious Gravity 5 1 instance 2 exposed
Issued
May 10, 2016
Abate by
Jun 8, 2016
Penalty
Initial $3,400 · Current $2,380 Reduced
29 CFR 1915.89(b):   The employers program did not cover procedures for lockout/tags-plus systems while servicing machinery, equipment, or systems.  Machine shop:  On or about 6 April 2016 and times prior thereto an energy isolation process was not established for the machinery in the shop.  Energy was not isolated on the martin 8" lathe that was hard wired to the electrical system of the facilities.  This condition exposed employees to a caught in hazard.
Recent events (2)
  • · I (S) $2380
  • · Z (S) $3400

1915.134 B

Serious Gravity 1 1 instance 3 exposed
Issued
May 10, 2016
Abate by
Jun 8, 2016
Penalty
Initial $2,550 · Current $1,785 Reduced
29 CFR 1915.134(b): Work rests were not kept a distance not to exceed 1/8 inch from the surface of the wheel.  Machine Shop:  On or about 6 April 2016 and times prior thereto, the work rest measured at 3/8 inch.  This exposed employees to struck-by hazard from work piece getting stuck between rest and wheel causing wheel to break.
Recent events (2)
  • · I (S) $1785
  • · Z (S) $2550

View Vigor Alaska Seward, LLC's full OSHA safety record →