SEWARD, AK ·
OSHA Inspection: VIGOR ALASKA SEWARD, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VIGOR ALASKA SEWARD, LLC in MILE 7 NASH ROAD, SEWARD, AK 99664 (NAICS 336611). OSHA activity number 341382059.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VIGOR ALASKA SEWARD, LLC
- Site address
- MILE 7 NASH ROAD
- City
- SEWARD
- State
- AK
- ZIP
- 99664
- Mailing
- MILE 7 NASH ROAD, SEWARD, AK 99664
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336611
- Employees
- 40
- Ownership type
- Private (A)
Citations
10 citations on file for this inspection.
1910.242 B
- Issued
- May 10, 2016
- Penalty
- Initial $2,550 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i. Machine shop: On or about 6 October 2015 and times prior thereto, an air nozzle did not have 30 P.S.I reducing device. This exposed employees to air embolism/laceration hazards if they contacted the discharge to their skin.
Recent events (2)
- · I (S) $1785
- · Z (S) $2550
1910.303 F02
- Issued
- May 10, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $2,550 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. (a) Generator/Air compressor Bldg: On or about 6 April 2016 and times prior thereto, the electrical panel P-227 was not properly identified with a listing for the circuits. This condition exposed employees to an electrical shock and burn hazard. (b) Docking Shack: On or about 6 April 2016 and times prior thereto, the electrical panel (number unknown) was not properly identified with a listing for the circuits. This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
- · I (S) $1785
- · Z (S) $2550
1910.303 G01
- Issued
- May 10, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment. Machine Shop, Latrine Closet: On or about 6 April 2016 and times prior thereto, a 480 volt electrical circuit breaker panel was not accessible to employees. This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 G02 I
- Issued
- May 10, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures. Machine shop: On or about 6 April 2016 and times prior thereto, the 480 volt Bus ducts had four locally fabricated wooden end caps installed and duct taped into place. This condition exposed employees to a fire hazard.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.304 G05
- Issued
- May 10, 2016
- Penalty
- Initial $2,550 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective. Coating Shop: On or about 6 April 2016 and times prior thereto, the electrical circuit consisting of 16 electrical outlets were not connected to a ground circuit. This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
- · I (S) $1785
- · Z (S) $2550
1910.305 B01 II
- Issued
- May 10, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $2,550 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed (a) Machine shop/tooling area: On or about 6 April 2016 and times prior thereto; A knockout plug was missing from a energized electrical outlet box. This condition exposed employees to electrical shock and electrical burn hazard. (b) Bldg 804/Electrical: On or about 6 April 2016 and times prior thereto; A knockout plug was missing from the energized entrance light switch. This condition exposed employees to electrical shock and electrical burn hazard.
Recent events (2)
- · I (S) $1785
- · Z (S) $2550
1910.305 J01 I
- Issued
- May 10, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located had live parts normally exposed to employee contact. (a) QA Room: On or about 6 April 2016 and times prior thereto, a 120 electrical outlet cover was missing on the south wall of the room. This condition exposed employees to an electrical shock and burn hazard. (b) Services Conex: On or about 6 April 2016 and times prior thereto, a 120 electrical outlet cover was missing on the conex. This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 J02 VI
- Issued
- May 10, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(vi): A receptacle installed in a wet location where the product intended to be plugged into it was not to be attended while in use (for example, sprinkler system controllers, landscape lighting, and holiday lights) did not have an enclosure that was weatherproof with the attachment plug cap inserted Old Tool room Building, back side: On Or About 6 April 2016 and times prior thereto, an electrical outlet was missing the waterproof cover. This condition exposed employees to an electrical shock hazard.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1915.89 B
- Issued
- May 10, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $3,400 · Current $2,380 Reduced
General-duty citation text
29 CFR 1915.89(b): The employers program did not cover procedures for lockout/tags-plus systems while servicing machinery, equipment, or systems. Machine shop: On or about 6 April 2016 and times prior thereto an energy isolation process was not established for the machinery in the shop. Energy was not isolated on the martin 8" lathe that was hard wired to the electrical system of the facilities. This condition exposed employees to a caught in hazard.
Recent events (2)
- · I (S) $2380
- · Z (S) $3400
1915.134 B
- Issued
- May 10, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $2,550 · Current $1,785 Reduced
General-duty citation text
29 CFR 1915.134(b): Work rests were not kept a distance not to exceed 1/8 inch from the surface of the wheel. Machine Shop: On or about 6 April 2016 and times prior thereto, the work rest measured at 3/8 inch. This exposed employees to struck-by hazard from work piece getting stuck between rest and wheel causing wheel to break.
Recent events (2)
- · I (S) $1785
- · Z (S) $2550
More inspections at Vigor Alaska Seward, LLC
View Vigor Alaska Seward, LLC's full OSHA safety record →
More inspections in this industry (NAICS 336611)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341382059.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.