Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BIA-WESTERN REGION

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of BIA-WESTERN REGION in PAPAGO AGENCY ROAD MAINTENANCE SHOP, CIRCLE DRIVE, BLDG 162, SELLS, AZ 85634 (NAICS 561210). OSHA activity number 341451110.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bia-Western Region — free Get an email when a new federal OSHA severe-injury report for Bia-Western Region is published. One employer, no account, unsubscribe in one click.
Establishment
BIA-WESTERN REGION
Site address
PAPAGO AGENCY ROAD MAINTENANCE SHOP, CIRCLE DRIVE, BLDG 162
City
SELLS
State
AZ
ZIP
85634
Mailing
2600 NORTH CENTRAL AVE. 4TH FLOOR, PHOENIX, AZ 85004
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
11
Ownership type
D

3 citations on file for this inspection.

1910.106 D02 I

Serious Gravity 1 1 instance 2 exposed
Issued
May 18, 2016
Abate by
Jun 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(2)(i): Approved container(s) or portable tank(s) were not used for the storage of flammable or combustible liquids:  (a) Road Maintenance Shop, Bldg. 162: On or about May 3, 2016, gasoline was stored in an unapproved propylene container. The standard specification of this container (ANSI/ASTM F852) was not a recognized test standard under OSHA's Nationally Recognized Testing Laboratory (NRTL) Program.
Recent events (1)
  • — Z (S) $0

1910.159 C02

Serious Gravity 1 1 instance 2 exposed
Issued
May 18, 2016
Abate by
Jun 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.159(c)(2): The employer did not properly maintain the installed automatic sprinkler system:  (a) Road Maintenance Shop, Bldg. 162: On or about May 3, 2016, the fire sprinkler system was last inspected August 2003. A main drain flow test was not performed annually and the inspector's test valve was not opened at least every two years to assure that the sprinkler system operates properly.
Recent events (1)
  • — Z (S) $0

1910.304 F01 IV

Serious Gravity 1 1 instance 2 exposed
Issued
May 18, 2016
Abate by
Jun 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:  (a) Road Maintenance Shop, Bldg. 162: On or about May 3, 2016, the circuit breaker panel was blocked by hoses, a cart and other items.
Recent events (1)
  • — Z (S) $0

View Bia-Western Region's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341451110.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.