SELLS, AZ —
OSHA Inspection: BIA-WESTERN REGION
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of BIA-WESTERN REGION in PAPAGO AGENCY FACILITY MANAGEMENT SHOP, CIRCLE DRIVE, BLDG 163, SELLS, AZ 85634 (NAICS 561210). OSHA activity number 341451136.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BIA-WESTERN REGION
- Site address
- PAPAGO AGENCY FACILITY MANAGEMENT SHOP, CIRCLE DRIVE, BLDG 163
- City
- SELLS
- State
- AZ
- ZIP
- 85634
- Mailing
- 2600 NORTH CENTRAL AVE. 4TH FLOOR, PHOENIX, AZ 85004
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561210
- Employees
- 11
- Ownership type
- D
Citations
11 citations on file for this inspection.
1910.22 B01
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(b)(1): Aisles and passageways were not kept clear and in good repair, with no obstruction across or in aisles that could create a hazard: (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, an electrical junction box was protruding from the concrete floor and created a tripping hazard.
Recent events (1)
- — Z (S) $0
1910.102 A
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.102(a): 29 CFR 1910.102(a) In-plant transfer, handling, storage, and/or use of acetylene in cylinders did not comply with the provisions of CGA Pamphlet G-1-2009 ("Acetylene"): (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, an acetylene gas cylinder in storage was not secured.
Recent events (1)
- — Z (S) $0
1910.106 D02 I
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(2)(i): Approved container(s) or portable tank(s) were not used for the storage of flammable or combustible liquids: (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, gasoline was stored in an unapproved propylene container. The standard specification of this container (ANSI/ASTM F852) is not a recognized test standard under OSHA's Nationally Recognized Testing Laboratory (NRTL) Program.
Recent events (1)
- — Z (S) $0
1910.215 B09
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, the tongue guard on the Baldor bench grinder was missing and the opening was approximately 1 inch.
Recent events (1)
- — Z (S) $0
1910.303 B01 IV
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(1)(iv): Electric equipment was not free from recognized hazards that were likely to cause serious physical harm to employees, such as damaged electrical insulation: (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, the power cord insulation of the 14 inch Makita cut-off saw was brittle and deteriorated which exposed the live conductors.
Recent events (1)
- — Z (S) $0
1910.303 G02 I
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, a cover was missing from the junction box which protruded from the concrete floor which exposed live electrical conductors.
Recent events (1)
- — Z (S) $0
1910.304 F01 IV
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, the circuit breaker panel was blocked by a refrigerator.
Recent events (1)
- — Z (S) $0
1910.159 C02
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(2): The employer did not properly maintain the installed automatic sprinkler system: (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, the fire sprinkler system was last inspected July 2003 and found to be non-compliant. The BIA was previously cited for a violation of this occupational safety and health standard which was contained in OSHA inspection number 927272 citation number 1, item number 2 and was affirmed as a final order on September 27, 2013, with respect to a workplace located at the Rick Lupe Fire Management Center, Whiteriver, AZ 85941.
Recent events (1)
- — Z (R) $0
1910.212 A01
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and automatic start up. (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, the chuck on the Rockwell 15-350 drill press was not guarded to protect employees from exposure to the rotating chuck. The BIA was previously cited for a violation of this occupational safety and health standard which was contained in OSHA inspection number 1056010 citation number 1, item number 7 and was affirmed as a final order on October 30, 2015, with respect to the BIA Maintenance Yard located at Fort Defiance, AZ 86504.
Recent events (1)
- — Z (R) $0
1910.215 A04
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, the work rest on the Baldor bench grinder was missing and the opening was approximate 1 inch. The BIA was previously cited for a violation of this occupational safety and health standard which was contained in OSHA inspection number 927403 citation number 1, item number 1 and was affirmed as a final order on October 10, 2013, with respect to a workplace located at 2 Elm Street, Whiteriver, AZ 85941.
Recent events (1)
- — Z (R) $0
1910.253 B04 III
- Issued
- May 18, 2016
- Abate by
- Jun 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m): (a) Facility Management Shop, Bldg. 163: On or about May 3, 2016, two oxygen cylinders were stored next to an acetylene cylinder. The BIA was previously cited for a violation of this occupational safety and health standard which was contained in OSHA inspection number 908522 citation number 1, item number 3B and was affirmed as a final order on July 9, 2013, with respect to a workplace located at Pyramid Lake Building Maintenance, 2008 Capitol Hill, Nixon, NV 89424.
Recent events (1)
- — Z (R) $0
More inspections at Bia-Western Region
View Bia-Western Region's full OSHA safety record →
More inspections in this industry (NAICS 561210)
More inspections in AZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341451136.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.