PHILLIPSBURG, NJ —
OSHA Inspection: AVANTOR PERFORMANCE MATERIALS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of AVANTOR PERFORMANCE MATERIALS in 600 NORTH BROAD STREET, PHILLIPSBURG, NJ 08865 (NAICS 325412). OSHA activity number 341471985.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AVANTOR PERFORMANCE MATERIALS
- Site address
- 600 NORTH BROAD STREET
- City
- PHILLIPSBURG
- State
- NJ
- ZIP
- 08865
- Mailing
- 600 NORTH BROAD STREET, PHILLIPSBURG, NJ 08865
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325412
- Employees
- 204
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.119 D03 I B
- Issued
- Nov 9, 2016
- Abate by
- Dec 7, 2016
- Penalty
- Initial $1,000 · Current $1,000
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): Information pertaining to the equipment in the process did not include Piping and Instrumentation Diagrams (P&IDs). Avantor Performance Materials 600 N. Broad Street, Phillipsburg, NJ site - The employer did not ensure that information pertaining to the process equipment was included on the P&IDs: a) Solvents Packaging Auto Fill - Bottles: Filter equipment that was observed in the field for Ethyl Acetate, NMP CAS#872-50-4, PRS-2000, PRS 3000, PRS-1000 and Methylene Chloride were not marked on P&ID 103-029 R10. P&ID 103-029 R10 showed F-01 and F-07 which were removed from the field. b) Acids Anhydrous Ammonia and Ammonium Hydroxide - Relief valve set pressures were marked incorrectly on the P&ID PLT-013. PSV2010 - PSV 2016 were recorded as (????????) on the P&ID when the correct pressure settings should have been 75 psig. Conditions noted on or about 9/8/2016.
Recent events (1)
- — Z (O) $1000
1910.119 L04
- Issued
- Nov 9, 2016
- Abate by
- Dec 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(l)(4): Process safety information required by paragraph (d) of this section was not updated when a change covered by this paragraph resulted in a change in the process safety information. Avantor Performance Materials 600 N. Broad Street, Phillipsburg, NJ site - a) Solvents Packaging Auto Fill - Bottles: Changes to the filter equipment that were observed in the field for Ethyl Acetate, NMP CAS#872-50-4, PRS-2000, PRS 3000, PRS-1000 and Methylene Chloride, were incorrect and did not reflect on P&ID 103-029 R10. The P&ID showed a previous configuration which included F-01 and F-07 which had beene removed from the field. MOCs were developed for these changes however the changes were not reflected on the process safety information. Conditions noted on or about 9/8/2016.
Recent events (1)
- — Z (O) $0
More inspections at Avantor Performance Materials
View Avantor Performance Materials's full OSHA safety record →
More inspections in this industry (NAICS 325412)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341471985.