Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: NEW PRIDE CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of NEW PRIDE CORPORATION in 1788 US HIGHWAY 61, FESTUS, MO 63028 (NAICS 326212). OSHA activity number 341494789.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NEW Pride Corporation for free Get an email when a new federal OSHA severe-injury report for NEW Pride Corporation is published. One employer, no account, unsubscribe in one click.
Site address
1788 US HIGHWAY 61
City
FESTUS
State
MO
ZIP
63028
Mailing
1788 US HIGHWAY 61, FESTUS, MO 63028
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326212
Employees
23
Ownership type
Private (A)

11 citations on file for this inspection.

1910.147 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Sep 28, 2016
Penalty
Initial $4,500 · Current $4,500
29 CFR 1910.147(c)(1):  The employer did not establish a program consisting of energy control procedures, employee training and periodic inspections to ensure that before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment would be isolated from the energy source and rendered inoperative in accordance with 29 CFR 1910.147(c)(4):    a/  The employer did not establish or implement a lockout/tagout program that consisted of specific procedures, devices, periodic inspections, or employee training.  Machinery serviced and maintained include, but are not limited to, the Branicks Spreader Machine, m/n EF, s/n unknown, Salisbury Buffing Machine, m/n 878, s/n unknown, and the Matrix Machine, m/n A66, s/n unknown.
Recent events (2)
  • · I (S) $4500
  • · Z (S) $4500

1910.147 C04 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Sep 28, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(4)(i):   Procedures were not developed, documented, and utilized for the control of potentially hazardous energy when employees are engaged in the activities covered by this section:    a/  Specific lockout/tagout procedures were not developed or implemented for machinery such as, but not limited to, the Salisbury Buffing Machine, m/n 878, s/n unknown, and the Matrix Machine, m/n A66, s/n unknown.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.147 C05 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 26, 2016
Abate by
Sep 28, 2016
Penalty
Initial $4,500 · Current $0 Reduced
29 CFR 1910.147(c)(5)(i):  Locks, tags, chains, wedges, key blocks, adapter pins, self-locking fasteners, or other hardware were not provided by the employer for isolating, securing or blocking of machines or equipment from energy sources:    a/  Suitable lockout/tagout devices were neither provided nor used for the effective isolation of compressed air or gravity for machinery such as Branicks Spreader Machine, m/n EF, s/n unknown, Salisbury Buffing Machine, m/n 878, s/n unknown, or theMatrix Machine, m/n A66, s/n unknown.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4500

1910.212 A01

Serious Gravity 5 2 instances 5 exposed
Issued
Jul 26, 2016
Abate by
Sep 7, 2016
Penalty
Initial $4,500 · Current $4,500
29 CFR 1910.212(a)(1):   One or more methods of machine guarding were not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    a/  At the Maintenance Table, the rotating parts belonging to the Central Machinery 10" Drill Press, m/n unknown, s/n 44836, were unguarded.    b/  At the Mold Area, the reciprocating motion of the mold belonging to the Matrix Machine, m/n A66, s/n unknown, was unguarded.
Recent events (2)
  • · I (S) $4500
  • · Z (S) $4500

1910.212 B

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 26, 2016
Abate by
Sep 7, 2016
Penalty
Initial $4,500 · Current $0 Reduced
29 CFR 1910.212(b):   Machines designed for a fixed location were not securely anchored to prevent walking or moving:    a/  At the Maintenance Table, the Central Machinery 10" Drill Press, m/n unknown, s/n 44836, was not anchored or secured against movement.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4500

1910.303 B07 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 26, 2016
Abate by
Sep 7, 2016
Penalty
Initial $4,500 · Current $4,500
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of electric equipment, such as parts that were broken, bent, cut or deteriorated by corrosion, chemical action, or overheating:  a/  Inside of the Final Inspection Area, the metallic, quad-receptacle box powering two branding irons was badly crushed to the point where the live conductors were exposed.
Recent events (2)
  • · I (S) $4500
  • · Z (S) $4500

1910.305 B01 I

Deleted Serious Gravity 5 2 instances 5 exposed
Issued
Jul 26, 2016
Abate by
Sep 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed:  a/  Inside of the Buffing Area, live conductors entered the Salisbury Buffing Machine, m/n 878, s/n unknown, through a circular opening that was approximately two inches wide.  The opening was not effectively closed.    b/  Inside of the Mold Area, a live conductor providing power to a guarded foot pedal entered the A2 Machine, m/n SB2, s/n 947060. The opening measured approximately 8"L X 4"H in size and was effectively closed.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B01 II

Serious Gravity 5 1 instance 5 exposed
Issued
Jul 26, 2016
Abate by
Sep 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii):  Unused openings in cabinets, boxes, and fittings were not effectively closed:  a/  Inside of the Arbitread Area, one, live, dual receptacle secured to a vertical column was missing a knockout.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B02 I

Serious Gravity 5 2 instances 5 exposed
Issued
Jul 26, 2016
Abate by
Sep 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i):  All pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose:  a/  Inside of the Maintenance Shop, specifically the north wall, one, live, receptacle box was not covered.  b/  Inside of the Inspection Area, specifically the north wall, one live, junction box was not covered.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 G01

Other-than-serious 2 instances 2 exposed
Issued
Jul 26, 2016
Abate by
Sep 7, 2016
Penalty
Initial $4,500 · Current $2,250 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    a/  Inside of the Buffing Area, a piece of cardboard approximately 15'L X 5'W in size was placed against two, 240 volt disconnect boxes.
Recent events (2)
  • · I (O) $2250
  • · Z (S) $4500

1910.305 G01 IV D

Other-than-serious 2 instances 1 exposed
Issued
Jul 26, 2016
Abate by
Sep 7, 2016
Penalty
Initial $4,500 · Current $2,250 Reduced
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces:    a/  Inside of the Final Inspection Area, two sets of yellow flexible cord were wrapped around the structural steel members of the building.  These flexible cords provided power to two branding irons, unknown make, model, or serial number.
Recent events (2)
  • · I (O) $2250
  • · Z (S) $4500

View NEW Pride Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341494789.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.