Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PACT TWO LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PACT TWO LLC in 2400 LUZERNE ST., SCRANTON, PA 18504 (NAICS 237110). OSHA activity number 341546679.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pact TWO LLC — free Get an email when a new federal OSHA severe-injury report for Pact TWO LLC is published. One employer, no account, unsubscribe in one click.
Establishment
PACT TWO LLC
Site address
2400 LUZERNE ST.
City
SCRANTON
State
PA
ZIP
18504
Mailing
PO BOX 74, RINGOES, NJ 08551
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237110
Employees
3
Ownership type
A

3 citations on file for this inspection.

1926.404 B01 I

Deleted Serious Gravity 1 1 instance 1 exposed
Issued
Jun 30, 2016
Abate by
Jul 13, 2016
Penalty
Initial $1,785 · Current $0 Reduced
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites:  a) Keyser Valley Pump Station, Scranton, PA: Flexible extension cords used to power portable hand tools were plugged into a receptacle inside the pump building and were not protected by GFCI or an AEGCP, as observed on or about June 15, 2016.  Abatement Certification Required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1785

1926.403 A

Deleted Serious Gravity 1 1 instance 2 exposed
Issued
Jun 30, 2016
Abate by
Aug 17, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.403(a): All electrical conductors and equipment were not approved:  a) Keyser Valley Pump Station, Scranton, PA: Messenger supported wiring (quadruplex) was utilized as a feeder from the pump building to the job trailer sub panel and was directly connected inside of the electrical boxes and attached to the wall of the pump building exposing the wiring to physical contact or damage, as observed on or about June 14, 2016.  Abatement Certification Required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.502 I03

Other-than-serious 1 instance 2 exposed
Issued
Jun 30, 2016
Abate by
Jul 13, 2016
Penalty
Initial $2,380 · Current $2,380
29 CFR 1926.502(i)(3): All covers were not secured when installed so as to prevent accidental displacement by the wind, equipment, or employees:    a) Keyser Valley Pump Station, Scranton, PA: Plywood installed to cover concrete vaults and manholes were not secured to prevent accidental displacement, as observed on or about June 14, 2016.    Abatement Certification Required.
Recent events (2)
  • — I (O) $2380
  • — Z (S) $2380

View Pact TWO LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341546679.