OREGON, OH —
OSHA Inspection: BP - HUSKY REFINING LLC
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of BP - HUSKY REFINING LLC in 4001 CEDAR POINT RD., OREGON, OH 43616 (NAICS 324110). OSHA activity number 341557528.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BP - HUSKY REFINING LLC
- Site address
- 4001 CEDAR POINT RD.
- City
- OREGON
- State
- OH
- ZIP
- 43616
- Mailing
- P.O. BOX 696, OREGON, OH 43697
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 400
- Ownership type
- A
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Sep 30, 2016
- Abate by
- Nov 28, 2016
- Penalty
- Initial $8,908 · Current $8,908
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees: Instance a): On or about June 9, 2016, the employer did not ensure the standard operating procedures for operating fire hydrants included language for depressurizing hydrants prior to removing hose connection caps. Instance b): On or about June 9, 2016, the employer did not ensure the operating procedure for fire hydrant use in the coker unit was properly implemented to ensure the permitting process for non emergency use was followed. Instance c): On or about June 9, 2016, the employer did not ensure mechanical integrity procedures used to test fire hydrants required fire suppression equipment to be tagged if deficiencies were found during routine inspection and testing. Instance d): On or about June 9, 2016, the employer did not ensure fire hydrant #33-20 was tagged due to deficiencies in the operation of the hose nozzle gate valve.
Recent events (2)
- — I (S) $8908
- — Z (S) $8908
1910.119 F03
- Issued
- Sep 30, 2016
- Abate by
- Oct 12, 2016
- Penalty
- Initial $8,908 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(f)(3): The operating procedures were not reviewed as often as necessary to assure that they reflected current operating practice, including changes that result from changes in process chemicals, technology, and equipment, and changes to facilities. The employer did not certify annually that these operating procedures are current and accurate. a. BP-Husky Refining, LLC located in Oregon, Ohio: On or about June 9, 2016, the employer did not ensure the operating procedure for fire hydrant operation ERT 018 was reviewed annually to ensure it reflected current operating practice.
Recent events (2)
- — I (S) $0
- — Z (S) $8908
1910.119 J02
- Issued
- Sep 30, 2016
- Abate by
- Oct 12, 2016
- Penalty
- Initial $8,908 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going integrity of process equipment. a. BP-Husky Refining, LLC located in Oregon, Ohio: On or about June 9, 2016, the employer did not ensure mechanical integrity procedures used to test fire hydrants required fire suppression equipment to be tagged if deficiencies were found during routine inspection and testing. b. BP-Husky Refining, LLC located in Oregon, Ohio: On or about June 9, 2016, the employer did not ensure fire hydrant inspection procedures were developed.
Recent events (2)
- — I (S) $0
- — Z (S) $8908
1910.119 J04 II
- Issued
- Sep 30, 2016
- Abate by
- Oct 12, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(j)(4)(ii): Inspection and testing procedures did not follow recognized and generally accepted good engineering practices. a. BP-Husky Refining, LLC located in Oregon, Ohio: On or about June 9, 2016, the employer did not ensure fire hydrant #33-20 was tagged due to deficiencies in the operation of the hose nozzle gate valve. b. BP-Husky Refining, LLC located in Oregon, Ohio: On or about June 9, 2016, the employer did not ensure fire hydrant inspection procedures were developed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
5(a)(1)
- Issued
- Sep 30, 2016
- Abate by
- Nov 28, 2016
- Penalty
- Initial $8,908 · Current $8,908
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the OSH Act: The employer did not correct deficiencies in equipment that were outside acceptable limits before further use or in a safe and timely manner when necessary means are taken to assure safe operation: a. BP-Husky Refining, LLC located in Oregon, Ohio: On or about June 9, 2016, the employer did not ensure the hose nozzle gate valve for hydrant #33-20 located near Coker 3 was repaired in a timely manner. On 6/17/2015 the broken valve was identified during an audit, entered into the company's work order system on 10/17/2015, and as of 6/9/2016 the gate valve still had not been repaired.
Recent events (2)
- — I (S) $8908
- — Z (S) $8908
More inspections at BP - Husky Refining LLC
View BP - Husky Refining LLC's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341557528.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.