TAMUNING, GU —
OSHA Inspection: J & B MODERN TECH
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of J & B MODERN TECH in 153 UNIT B, EAST HARMON IND'L PARK, TAMUNING, GU 96913 (NAICS 493110). OSHA activity number 341711448.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- J & B MODERN TECH
- Site address
- 153 UNIT B, EAST HARMON IND'L PARK
- City
- TAMUNING
- State
- GU
- ZIP
- 96913
- Mailing
- PO BOX 9788, TAMUNING, GU 96931
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 32
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.303 B02
- Issued
- Oct 20, 2016
- Penalty
- Initial $2,147 · Current $1,503 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. (a) At the materials and supplies warehouse, a square box with pre-punched knockout was used at the end of the flexible cord.
Recent events (2)
- — I (S) $1502.9
- — Z (S) $2147
1910.303 B07 I
- Issued
- Oct 20, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused opening in electrical cabinets were not effectively closed provide substantially equivalent protection to the equipment. (a) At the materials and supplies warehouse, a knockout is missing on the junction box of the lockformer equipment. (b) At the materials and supplies warehouse, a knockout is missing on the main electrical power panel.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Oct 20, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Covers of outlet boxes having holes through which flexible cord pendants passed were not provided with bushings designed for the purpose nor did the holes have smooth, well-rounded surfaces on which the cords could bear. (a) At the materials and supplies warehouse, the black flexible cord fed through the main electrical power panel did not have a bushing installed for the cords protection.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Oct 20, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws. (a) At the materials and supplies warehouse, the Lincoln 1000 tomahawk welder's power cord did not have strain relief, insulation was separating from the plug.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A02 II
- Issued
- Oct 20, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service: (a) At the materials and supplies warehouse, the orange with black striped extension cord on top of the lock former had torn insulation and the plug is missing its ground prong.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.22 B02
- Issued
- Oct 20, 2016
- Abate by
- Nov 16, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(b)(2): Permanent aisles and passageways were not appropriately marked: (a) At the materials and parts warehouse, permanent aisles and passageways where material handling equipment were utilized, were not appropriately marked.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.22 D01
- Issued
- Oct 20, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate. (a) At the mezzanine/upper storage room used for parts and materials storage, the maximum load capacity limit was not posted in a conspicuous place.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at J & B Modern Tech
View J & B Modern Tech's full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in GU
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341711448.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.