Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NOMAC DRILLING LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NOMAC DRILLING LLC in 30.9 MILES NORTHWEST OF PECOS, TX RIG #22, PECOS, TX 79772 (NAICS 213111). OSHA activity number 341880920.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nomac Drilling LLC — free Get an email when a new federal OSHA severe-injury report for Nomac Drilling LLC is published. One employer, no account, unsubscribe in one click.
Establishment
NOMAC DRILLING LLC
Site address
30.9 MILES NORTHWEST OF PECOS, TX RIG #22
City
PECOS
State
TX
ZIP
79772
Mailing
3400 SOUTH RADIO ROAD, EL RENO, OK 73036
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213111
Employees
300
Ownership type
A

2 citations on file for this inspection.

1910.304 B03 II C 3

Other-than-serious 1 instance 3 exposed
Issued
Mar 13, 2017
Abate by
Mar 30, 2017
Penalty
Initial $777 · Current $777
29 CFR 1910.304(b)(3)(ii)(C)(3): Each cord set, attachment cap, plug, and receptacle of cord sets, and any equipment connected by cord and plug, was not visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage:  Drilling Rig 22: On or about October 19, 2016 a portable electrical fan in the mixing trailer had damage to the cord insulation.  The cord was not visually inspected from insulation damage, this condition exposed employees to an electrical shock hazard.
Recent events (1)
  • — Z (O) $777

1910.305 A02 XI

Other-than-serious 1 instance 3 exposed
Issued
Mar 13, 2017
Abate by
Mar 30, 2017
Penalty
Initial $777 · Current $777
29 CFR 1910.305(a)(2)(xi): Cable assemblies and flexible cords and cables were not supported in place at intervals that ensure that they will be protected from physical damage:  Drilling Rig 22: On or about October 19, 2016 flexible cords feeding the SCR above the entrance door were not supported and rubbed against the edges of the door when opened, this condition exposed employees to an electrical shock hazard.
Recent events (1)
  • — Z (O) $777

View Nomac Drilling LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341880920.