HAVERHILL, MA —
OSHA Inspection: HANS KISSLE COMPANY, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of HANS KISSLE COMPANY, LLC in 9 CREEK BROOK DRIVE, HAVERHILL, MA 01832 (NAICS 311991). OSHA activity number 341984581.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HANS KISSLE COMPANY, LLC
- Site address
- 9 CREEK BROOK DRIVE
- City
- HAVERHILL
- State
- MA
- ZIP
- 01832
- Mailing
- 9 CREEK BROOK DRIVE, HAVERHILL, MA 01832
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311991
- Employees
- 350
- Ownership type
- A
Citations
14 citations on file for this inspection.
1910.119 D03 I B
- Issued
- Jun 15, 2017
- Abate by
- Oct 2, 2017
- Penalty
- Initial $9,054 · Current $5,400 Reduced
0170
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the piping and instrumentation diagram for the ammonia refrigeration process did not depict the oil pot in the mechanical room.
Recent events (2)
- — I (S) $5400
- — Z (S) $9054
1910.119 D03 I D
- Issued
- Jun 15, 2017
- Abate by
- Oct 2, 2017
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): Process safety information pertaining to the equipment in the process did not include relief system design and design basis: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the relief system design and design basis for the ammonia refrigeration system have not been documented.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 D03 II
- Issued
- Jun 15, 2017
- Abate by
- Jul 20, 2017
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(d)(3)(ii): Compliance with recognized and generally accepted good engineering practices was not documented: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, compliance with recognized and generally accepted good engineering practices (RAGAGEP) was not documented in that the doors of the ammonia refrigeration system mechanical room were not provided with panic-type hardware, were not tight-fitting, and did not open outward. The facility's chosen RAGAGEP, ANSI/IIAR 2-1992, requires that ammonia refrigeration mechanical rooms shall have tight-fitting doors which open outward and are provided with panic type hardware. This requirement is described at Section 4.4.8 of ANSI/IIAR 2 - 1992.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 E03 I
- Issued
- Jun 15, 2017
- Abate by
- Feb 1, 2018
- Penalty
- Initial $9,054 · Current $5,400 Reduced
0170
General-duty citation text
29 CFR 1910.119(e)(3)(i): The process hazard analysis did not address the hazards of the process: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the hazards of the anhydrous ammonia refrigeration process, such as those associated with the accumulation of noncondensable gases within the process, have not been adequately addressed by the facility through process hazard analysis.
Recent events (2)
- — I (S) $5400
- — Z (S) $9054
1910.119 E03 IV
- Issued
- Jun 15, 2017
- Abate by
- Feb 1, 2018
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(e)(3)(iv): The process hazard analysis did not address the consequences of failure of engineering and administrative controls: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the consequences of failure of engineering and administrative controls associated with the anhydrous ammonia refrigeration process, such as, but not limited to ammonia sensors, pressure relief valves, and daily rounds, have not been adequately addressed by the facility through process hazard analysis.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 E03 V
- Issued
- Jun 15, 2017
- Abate by
- Feb 1, 2018
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(e)(3)(v): The process hazard analysis did not address facility siting: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, facility siting for the anhydrous ammonia refrigeration process, such as location of ammonia refrigeration process equipment and associated piping in proximity to high pressure boilers subjected the equipment to impact in the event of catastrophic high pressure boiler failure, has not been adequately addressed by the facility through process hazard analysis.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 F01 I B
- Issued
- Jun 15, 2017
- Abate by
- Oct 2, 2017
- Penalty
- Initial $9,054 · Current $5,400 Reduced
0170
General-duty citation text
29 CFR 1910.119(f)(1)(i)(B): Written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information addressing normal operations have not been developed and implemented: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, written procedures for collecting and interpreting ammonia refrigeration system log information have not been developed.
Recent events (2)
- — I (S) $5400
- — Z (S) $9054
1910.119 J04 IV
- Issued
- Jun 15, 2017
- Abate by
- Oct 2, 2017
- Penalty
- Initial $9,054 · Current $5,400 Reduced
0170
General-duty citation text
29 CFR 1910.119(j)(4)(iv): The documentation of each inspection and test that was performed on the process did not identify the date of the inspection or test, the name of the person who performed the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test performed, and the results of the inspection or test: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the most recent occurrence of ammonia sensor calibration has not been documented. (b) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, documentation of previous occurrences of ammonia sensor calibration does not include the serial number or other identifier of the ammonia sensors calibrated, a description of the calibration performed, and the results of the calibration. (c) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, inspections of refrigerant piping do not result in documentation containing a unique identifier of the piping inspected, a description of the inspection performed, and the results of the inspection.
Recent events (2)
- — I (S) $5400
- — Z (S) $9054
1910.119 L01
- Issued
- Jun 15, 2017
- Abate by
- Oct 2, 2017
- Penalty
- Initial $9,054 · Current $5,400 Reduced
0170
General-duty citation text
29 CFR 1910.119(l)(1): Procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affect a covered process have not been implemented: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, procedures to manage changes related to procedures and changes to facilities that affect the ammonia refrigeration system have not been implemented.
Recent events (2)
- — I (S) $5400
- — Z (S) $9054
1910.119 N
- Issued
- Jun 15, 2017
- Abate by
- Aug 15, 2017
- Penalty
- Initial $9,054 · Current $5,400 Reduced
0170
General-duty citation text
29 CFR 1910.119(n): An emergency plan was not established for the entire plant in accordance with the provisions of 29 CFR 1910.38: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the emergency action plan established for the facility does not address procedures for reporting a fire or other emergency, employee rescue or medical duties, and information for who may be contacted by employees who need more information about the plan or an explanation of their duties under the plan as required by 29 CFR 1910.38(c) items 1, 3, and 6.
Recent events (2)
- — I (S) $5400
- — Z (S) $9054
1910.38 C01
- Issued
- Jun 15, 2017
- Abate by
- Aug 15, 2017
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.38(c)(1): The emergency action plan did not include procedures for reporting a fire or other emergency: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the facility's emergency action plan does not contain procedures for reporting a fire or other emergency.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.38 C05
- Issued
- Jun 15, 2017
- Abate by
- Aug 15, 2017
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.38(c)(5): The emergency action plan did not include procedures to be followed by employees performing rescue or medical duties: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the facility's emergency action plan did not include procedures to be followed by employees performing rescue or medical duties, including a prohibition from participating in such activities if applicable.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.38 C06
- Issued
- Jun 15, 2017
- Abate by
- Aug 15, 2017
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.38(c)(6): The emergency action plan did not include the name or job title of every employee who may be contacted by employees who need more information about the plan or an explanation of their duties under the plan: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, the facility's emergency action plan does not include the name or job title of every employee who may be contacted by employees who need more information about the plan or an explanation of their duties under the plan.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.120 Q01
- Issued
- Jun 15, 2017
- Abate by
- Aug 15, 2017
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.120(q)(1): An emergency response plan to handle anticipated emergencies prior to commencement of emergency response operations has not been developed and implemented: (a) Location - 9 Creek Brook Drive, Haverhill, MA: On or about 12/20/2016, an emergency response plan has not been developed in order to address anticipated emergencies related to the operation of an industrial ammonia refrigeration system.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Hans Kissle Company, LLC
View Hans Kissle Company, LLC's full OSHA safety record →
More inspections in this industry (NAICS 311991)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341984581.