OSHA Inspection: HILL AIR FORCE BASE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of HILL AIR FORCE BASE in 309 AMXG BUILDING 680, HILL AIR FORCE BASE, UT 84056 (NAICS 928110). OSHA activity number 341997062.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hill AIR Force Base — free Get an email when a new federal OSHA severe-injury report for Hill AIR Force Base is published. One employer, no account, unsubscribe in one click.
Establishment
HILL AIR FORCE BASE
Site address
309 AMXG BUILDING 680
City
HILL AIR FORCE BASE
State
UT
ZIP
84056
Mailing
75 AW OCC. SAFETY MANAGER ATTN: RONALD JAMES 7285 4TH STREET BUILDING 180, HILL AIR FORCE BASE, UT 84056
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
9000
Ownership type
D

2 citations on file for this inspection.

1910.107 D07

Serious Gravity 1 1 instance 150 exposed
Issued
Mar 29, 2017
Abate by
May 3, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.107(d)(7): Exhaust ducts were not constructed of steel:  (a) Hill Air Force Base, at Building 680, Hill Air Force Base, UT:  On and preceding 12/20/16, The employer did not ensure that exhaust ducts used to ventilate the paint spraying enclosure were constructed of steel.  Employees sprayed coatings and primers containing flammable liquids within an enclosure.  The paint enclosure was constructed of plastic sheeting and PVC pipe as the frame.  The enclosure was provided with a portable exhaust and filtration unit.  The exhaust ducts used to ventilate the enclosure were constructed of flexible plastic.  This condition exposed employees to a fire hazard.
Recent events (1)
  • — Z (S) $0

1910.157 D04

Serious Gravity 1 1 instance 150 exposed
Issued
Mar 29, 2017
Abate by
May 3, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.157(d)(4): Portable fire extinguishers for use on Class B fires were not distributed so that the travel distance from the Class B hazard area to any extinguisher was 50 feet or less:  (a) Hill Air Force Base, at Building 680, Hill Air Force Base, UT:  On and preceding 12/20/16, the employer did not ensure that adequate fire extinguishers were distributed so that the travel distance from the Class B hazard area to any extinguisher was 50 feet or less.  Employees sprayed primers and coatings containing flammable liquids within an enclosure constructed of plastic sheeting and PVC piping.  The enclosure was not provided with an immediately accessible means of fire protection.  This spray painting enclosure was located approximately 166 feet from the nearest portable fire extinguisher.  This condition exposed employees to a fire hazard.