HUNTLEY, IL —
OSHA Inspection: ROHRER CORPORATION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ROHRER CORPORATION in 13701 GEORGE BUSH COURT, HUNTLEY, IL 60142 (NAICS 326199). OSHA activity number 342014750.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ROHRER CORPORATION
- Site address
- 13701 GEORGE BUSH COURT
- City
- HUNTLEY
- State
- IL
- ZIP
- 60142
- Mailing
- 13701 GEORGE BUSH COURT, HUNTLEY, IL 60142
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 119
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.212 A01
- Issued
- Jul 7, 2017
- Abate by
- Oct 4, 2017
- Penalty
- Initial $9,959 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are-barrier guards, two-hand tripping devices, electronic safety devices, etc.: a. Thermoformer Series 2500 Stackers - On or about 11 January 2017, on each stacker of the thermoformer lines, the employees had were exposed to inadvertent contact with moving parts while required to remove product. This exposed employees to struck-by and caught-in hazards. b. Wheeler Plastic Compactor waste dumpster lift - On or about 11 January 2017, the waste dumpster lift was not guarded to prevent employees from being caught-in and crushed by the dumpster bin when it is lowered. Employees walking and working the area were not guarded against accidental/incidental entry into such areas. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $5000
- — Z (S) $9959
1910.332 B01
- Issued
- Jul 7, 2017
- Abate by
- Aug 4, 2017
- Penalty
- Initial $9,959 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments: On or about 11 January 2017, and on dates prior, employees were required to work on electrical equipment from 110-480 volts. Employees were running 3 new electrical lines that were rated at 480volts. Employees were required to test the lines to ensure they were not live. Employees were not provided with the appropriate Personal Protective Equipment or tools to protect themselves. The employees were not trained in and familiar with safety-related work practices, such as the use of special precautionary techniques, personal protective equipment (PPE), and insulating and shielding materials. The employees were exposed to shock and arc flash hazards. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $5000
- — Z (S) $9959
1910.333 C02
- Issued
- Jul 7, 2017
- Abate by
- Aug 4, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(c)(2): Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools: On or about 11 January 2017, and on dates prior, unqualified employees were required to work on electrical equipment from 110-480 volts. Employees were running three new electrical lines that were rated at 480volts. Employees were required to test the lines to ensure they were not live. The employees were not capable of safely performing such work and were not trained in and were not familiar with safety-related work practices, including the use of special precautionary techniques, Personal Protective Equipment (PPE), and insulating and shielding materials. The employees were exposed to shock and arc flash hazards. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 C01
- Issued
- Jul 7, 2017
- Abate by
- Aug 4, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(c)(1): Only qualified persons may perform testing work on electric circuits or equipment: On or about 11 January 2017, and on dates prior, unqualified employees were required to work on electrical equipment from 110-480 volts. Employees were running three new electrical lines that were rated at 480volts. Employees were required to test the lines to ensure they were not live. Employees were not qualified to safely perform such tasks. The employees were exposed to shock and electrocution hazards. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 A
- Issued
- Jul 7, 2017
- Abate by
- Aug 11, 2017
- Penalty
- Initial $9,959 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards: On or about 11 January 2017, and on dates prior, employees were required to work on electrical equipment from 110-480 volts. Employees were running three new electrical lines that were rated at 480volts. Employees were required to test the lines to ensure they were not live. Electrically insulated rubber gloves were not provided to prevent direct or indirect contract with live electrical parts. Employees did not employ other safety related work practices including adequate equipment and tools to protect themselves from electrocution and shock hazards. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $5000
- — Z (S) $9959
1910.335 A01 I
- Issued
- Jul 7, 2017
- Abate by
- Aug 4, 2017
- Penalty
- Initial $9,959 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed: On or about 11 January 2017, and on dates prior, employees were required to work on electrical equipment from 110-480 volts. Employees were running three new electrical lines that were rated at 480volts each. Employees were required to perform voltage testing on the lines. The employer failed to provide electrical protective equipment appropriate for the specific parts of the body to be protected when they were performed such tasks in areas where they had the potential to come into contact with energized equipment or encounter arc flash hazards. Employees did not wear appropriate electrical protective equipment, including but not limited to the following, to protect against electrical shock injuries: a) Rubber insulating gloves with leather protectors b) Arc-Rated clothing such as arc-rated long-sleeve shirt and pants, or arc-rated coverall c) Hearing protection (canal inserts) d) Arc-Rated flash suit, hood or balaclava Abatement documentation is required of this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $5000
- — Z (S) $9959
1910.335 A01 IV
- Issued
- Jul 7, 2017
- Abate by
- Jul 31, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(iv): Employees shall wear nonconductive head protection wherever there is a danger of head injury from electric shock or burns due to contact with exposed energized parts. Maintenance employee(s) did not wear nonconductive head protection, such as a hard hat with dielectric properties to protect against electrical shock or injuries in case of contact with energized equipment. On or about 11 January 2017, and on dates prior, employees were required to work on electrical equipment from 110-480 volts. Employees were running 3 new electrical lines that were rated at 480volts each. Employees were required to test the lines to ensure they were not live. Employees were not provided with the appropriate Personal Protective Equipment, tools, or training to protect themselves. The employees were not trained in and familiar with safety-related work practices, such as the use of special precautionary techniques, Personal Protective Equipment (PPE), and insulating and shielding materials. The employees were exposed to shock hazards. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 V
- Issued
- Jul 7, 2017
- Abate by
- Jul 31, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees shall wear protective equipment for the eyes or face wherever there is danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion. Maintenance employee(s) did not wear appropriate protective equipment, such as safety glasses and an arc-rated face shield, to protect the eyes and face against electrical arc flash/blast injuries. On or about 11 January 2017, and on dates prior, employees were required to work on electrical equipment from 110-480 volts. Employees were running 3 new electrical lines that were rated at 480volts each. Employees were required to test the lines to ensure they were not live. Employees were not provided with the appropriate Personal Protective Equipment, tools, or training to protect themselves. The employees were not trained in and familiar with safety-related work practices, such as the use of special precautionary techniques, Personal Protective Equipment (PPE), and insulating and shielding materials. The employees were exposed to shock and arc flash hazards. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 B02 I
- Issued
- Jul 7, 2017
- Abate by
- Aug 4, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer shall maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives: The employer did not maintain written procedures to ensure parts were de-energized, locked out and tagged in accordance with paragraph (b). On or about 11 January 2017, and on dates prior, employees were required to work on electrical equipment from 110-480 volts. Employees were running three new electrical lines that were rated at 480volts each. Employees were required to perform voltage tests on the lines without written procedures to perform such inspections. This exposed employee(s)to electric shock/electrocution and arc flash/blast hazards. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Rohrer Corporation
View Rohrer Corporation's full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342014750.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.