ALGONA, IA —
OSHA Inspection: DEPT OF AGRICULTURE - FARM SERVICE AGENCY
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of DEPT OF AGRICULTURE - FARM SERVICE AGENCY in 605 EAST STATE, SUITE 1, ALGONA, IA 50511 (NAICS 926140). OSHA activity number 342205879.
Where did this inspection happen?
- Establishment
- DEPT OF AGRICULTURE - FARM SERVICE AGENCY
- Site address
- 605 EAST STATE, SUITE 1
- City
- ALGONA
- State
- IA
- ZIP
- 50511
- Mailing
- P.O. BOX 578, ALGONA, IA 50511
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 926140
- Employees
- 11
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.303 B01
- Issued
- May 1, 2017
- Abate by
- May 15, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: (a) In the Kitchenette/break room, a receptacle outlet was not provided with ground-fault circuit-interrupter (GFCI) protection for personnel when the outlet was located within 18 inches of a sink, exposing employees to an electrical hazard. One feasible Means of Abatement: Install a GFCI to replace the standard outlet or series connect the outlet to the GFCI on the opposite side of the sink in accordance with NFPA 70 - National Electric Code, Article 210.8(B)(5).
Recent events (1)
- — Z (S) $0
1910.304 B04 II B
- Issued
- May 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4: (a) In the kitchenette/break area, an APC type 3 SPD Power Tap rated 15 amp was furnishing power to a Sharp Microwave Model R-305HW Serial 223396 rated 13.5 amp, exceeded the allowable safe loading capacity of the RPT and receptacle.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- May 1, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) In the kitchenette/break area, an APC type 3 SPD Relocatable Power Tap was used as an extension cord and was furnishing power to a Sharp Microwave Model R-305HW Serial 223396.
Recent events (1)
- — Z (S) $0
More inspections at Dept OF Agriculture - Farm Service Agency
View Dept OF Agriculture - Farm Service Agency's full OSHA safety record →