Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SAPUTO DAIRY FOODS USA, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SAPUTO DAIRY FOODS USA, LLC in 100 MILK LANE, NEWINGTON, CT 06111 (NAICS 311511). OSHA activity number 342792140.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Saputo Dairy Foods USA, LLC — free Get an email when a new federal OSHA severe-injury report for Saputo Dairy Foods USA, LLC is published. One employer, no account, unsubscribe in one click.
Site address
100 MILK LANE
City
NEWINGTON
State
CT
ZIP
06111
Mailing
100 MILK LANE, NEWINGTON, CT 06111
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311511
Employees
100
Ownership type
A

9 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 1 instance 4 exposed
Issued
Jan 10, 2018
Abate by
Feb 28, 2018
Penalty
Initial $6,911 · Current $4,147 Reduced
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by pinch points and point of operation:   Corrugate Warehouse:  On, or about, November 13, 2017, the Vertech M-60 vertical baler was not provided with an interlock on the lower door and a requirement that a positive pressure control be used to move the ram when the lower door was open.
Recent events (2)
  • — I (S) $4146.6
  • — Z (S) $6911

1910.215 A04

Other-than-serious 1 instance 4 exposed
Issued
Jan 10, 2018
Penalty
Initial $4,405 · Current $0 Reduced
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:     Maintenance Shop, Weld Booth:  On, or about, November 13, 2017, the work rest provided on the JET off-hand grinder, serial number 09020095, was adjusted approximately .5 inch from the abrasive wheel.
Recent events (2)
  • — I (O) $0
  • — Z (S) $4405

1910.215 B09

Other-than-serious 1 instance 4 exposed
Issued
Jan 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:     Maintenance Shop, Weld Booth:  On, or about, November 13, 2017, the tongue guard provided on the JET off-hand grinder, serial number 09020095, was adjusted approximately 1.25 inches from the abrasive wheel.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 1 3 instances 2 exposed
Issued
Jan 10, 2018
Penalty
Initial $4,405 · Current $2,643 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:   On, or about, November 13, 2017, in the following locations, covers had not been re-installed on electrical enclosures:  A.    MCC Room near Plant Entrance:  Covers were not installed at the top of the Allen-Bradley 480 volt motor control center and also on horizontal wall mounted raceway located above the motor control center enclosure.  B.     Main Electrical Room:  A large Westinghouse 480 volt circuit breaker enclosure was missing to vent louvers on the right side.  C.     Small Electrical Room:  A cover was missing from the top of the Allen-Bradley 480 volt motor control center and a section of raceway was not provided with a cover above the entrance door.
Recent events (2)
  • — I (S) $2643
  • — Z (S) $4405

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 10, 2018
Penalty
Initial $8,638 · Current $5,183 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  Main Electrical Room:  On, or about, November 13, 2017, the trim piece was not installed on Panel 10, a Westinghouse 240 volt panelboard.
Recent events (2)
  • — I (S) $5182.8
  • — Z (S) $8638

1910.305 D02

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(d)(2): Panel boards were not dead front:  Main Electrical Room:  On, or about, November 13, 2017, four circuit breakers installed in Panel V 10 1, a Westinghouse panelboard, were not provided with covers over the openings provided in the front of the breakers.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 10, 2018
Penalty
Initial $6,911 · Current $4,147 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  Allen-Bradley MCC Room near Plant Entrance:  On, or about, November 11, 2017, an employee opened a 480 volt motor control center bucket to reset the controls.  The employee was not wearing a fire resistive balaclava.
Recent events (2)
  • — I (S) $4146.6
  • — Z (S) $6911

1910.335 A01 II

Serious Gravity 5 2 instances 1 exposed
Issued
Jan 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(ii): Protective equipment was not maintained in a safe, reliable condition and/or was not periodically inspected or tested:  Allen-Bradley MCC Room near Plant Entrance:  On, or about, November 11, 2017, an employee opened a 480 volt motor control center to reset the controls.  The Salisbury Category 0 voltage rated gloves that were provided for use had not been inspected in the previous six months.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Other-than-serious 1 instance 4 exposed
Issued
Jan 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    Maintenance Shop:  On, or about, November 13, 2017, a machine part was stored on the floor in front of Panel 71, a General Electric 480 volt panelboard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Saputo Dairy Foods USA, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342792140.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.