Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MERRILL INDUSTRIES, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MERRILL INDUSTRIES, LLC in 26 VILLAGE STREET, ELLINGTON, CT 06029 (NAICS 322211). OSHA activity number 343024055.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Merrill Industries, LLC — free Get an email when a new federal OSHA severe-injury report for Merrill Industries, LLC is published. One employer, no account, unsubscribe in one click.
Site address
26 VILLAGE STREET
City
ELLINGTON
State
CT
ZIP
06029
Mailing
P.O. BOX 150, ELLINGTON, CT 06029
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322211
Employees
40
Ownership type
A

9 citations on file for this inspection.

1910.147 C01

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 6, 2018
Abate by
Sep 3, 2018
Penalty
Initial $5,174 · Current $2,587 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:     Plant-wide:  On, or about, March 19, 2018, the company had not developed and implemented a lock out/tag out program to protect employees during servicing and maintenance of equipment.
Recent events (2)
  • — I (S) $2587
  • — Z (S) $5174

1910.303 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 6, 2018
Abate by
May 23, 2018
Penalty
Initial $5,174 · Current $2,587 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:  Production Floor:  On, or about, March 19, 2018, the DC motor drive located at the Koppers Print and Slot machine was not provided with side covers, exposing live parts such as fuse holders and terminal screws.
Recent events (2)
  • — I (S) $2587
  • — Z (S) $5174

1910.305 G02 III

Serious Gravity 1 2 instances 2 exposed
Issued
Apr 6, 2018
Abate by
May 23, 2018
Penalty
Initial $3,880 · Current $1,940 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  Glue Room:  On, or about, March 19, 2018, buss drop cables supplying the following machines were not provided with proper strain relief:  A.  Gray Gluer. B.  Blue Gluer.
Recent events (2)
  • — I (S) $1940
  • — Z (S) $3880

1910.332 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 6, 2018
Abate by
May 23, 2018
Penalty
Initial $6,467 · Current $3,234 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    Company:  On, or about, March 19, 2018, maintenance personnel had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing live trouble-shooting and verifying whether or not electrical equipment was properly de-energized.
Recent events (2)
  • — I (S) $3233.5
  • — Z (S) $6467

1910.335 A01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 6, 2018
Abate by
Sep 3, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    Company:  On, or about, March 19, 2018, personal protective equipment such as, but not limited to, fire resistive clothing, face shields, balaclavas, hard hats and hearing protection were not provided to employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 II

Serious Gravity 1 1 instance 1 exposed
Issued
Apr 6, 2018
Abate by
May 23, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(ii): Protective equipment was not maintained in a safe, reliable condition and/or was not periodically inspected or tested:    Company:  On, or about, March 19, 2018, a pair of Class 00 Salisbury voltage rated gloves had not been inspected in the previous six months in accordance with 29 CFR 1910.137.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 E01

Other-than-serious 1 instance 5 exposed
Issued
Apr 6, 2018
Abate by
May 23, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.36(e)(1): A side-hinged door was not used to connect any room to an exit route:   CAD Room:  On, or about, March 19, 2018, the sliding door that led to the CAD Room was marked as an Exit.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.36 G02

Other-than-serious 2 instances 5 exposed
Issued
Apr 6, 2018
Abate by
May 23, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.   On, or about, March 19, 2018, in the following locations, access to exits was less than 28 inches wide:  A.    CAD Room. B.     Compressor Area.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 B07 I

Other-than-serious 1 instance 2 exposed
Issued
Apr 6, 2018
Abate by
May 23, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:     Production Floor, Koppers Print and Slot Machine:  Tape was used to cover an opening in the GE column mounted circuit breaker panel at position 15.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Merrill Industries, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343024055.