Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GENPAK, LLC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of GENPAK, LLC. in 845 KADERLY DRIVE, COLUMBUS, OH 43228 (NAICS 326199). OSHA activity number 343099552.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Genpak, LLC. — free Get an email when a new federal OSHA severe-injury report for Genpak, LLC. is published. One employer, no account, unsubscribe in one click.
Establishment
GENPAK, LLC.
Site address
845 KADERLY DRIVE
City
COLUMBUS
State
OH
ZIP
43228
Mailing
845 KADERLY DRIVE, COLUMBUS, OH 43228
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
100
Ownership type
A

2 citations on file for this inspection.

1910.303 F02

Other-than-serious 1 instance 1 exposed
Issued
Jul 17, 2018
Penalty
Initial $10,163 · Current $10,163
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident.    a. On or about April 14, 2018, located in the outdoor substation, the employer did not ensure that the main switches on the 15,000 VAC Square D switchgear were properly labeled to indicate the equipment which it serviced.
Recent events (2)
  • — I (O) $10163
  • — Z (S) $10163

1910.333 B02 II A

Other-than-serious 1 instance 1 exposed
Issued
Jul 17, 2018
Abate by
Aug 20, 2018
Penalty
Initial $10,163 · Current $10,163
29 CFR 1910.333(b)(2)(ii)(A): Safe procedures for deenergizing circuits and equipment shall be determined before circuits or equipment are deenergized.    a. On or about April 14, 2018, located in the indoor substation, an employee was performing preventative maintenance work on electrical distribution switchboards. The employer did not ensure that energy control procedures were utilized to ensure that 1910.333(a)-(c) work practices were employed, such as, but not limited to, reviewing electrical circuits, determining electrical personal protective equipment requirements, procedures for verification of de-energized parts, use and application of grounding equipment, and application of lockout devices by exposed employees.
Recent events (2)
  • — I (O) $10163
  • — Z (S) $10163

View Genpak, LLC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343099552.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.