SEGUIN, TX —
OSHA Inspection: FCA LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of FCA LLC in 2348 FM 464, SEGUIN, TX 78155 (NAICS 321920). OSHA activity number 343441085.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FCA LLC
- Site address
- 2348 FM 464
- City
- SEGUIN
- State
- TX
- ZIP
- 78155
- Mailing
- 2348 FM 464, SEGUIN, TX 78155
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321920
- Employees
- 47
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.147 D05 I
- Issued
- Sep 19, 2018
- Abate by
- Sep 25, 2018
- Penalty
- Initial $12,934 · Current $7,760 Reduced
General-duty citation text
29 CFR 1910.147(d)(5)(i): All potentially hazardous stored or residual energy was not relieved, disconnected, restrained or otherwise rendered safe after the application of lockout or tagout devices to energy isolating devices: On or about August 27, 2018, at the dust collector, the employer failed to ensure potential energy was rendered safe. The employer did not have in place energy control procedures to stop the paddle wheel from turning from the weight of the sawdust in the hopper. Employees exposed to an amputation hazard from being struck by the unexpected turning of the paddle wheel blade from the gravitation force of the sawdust in the hopper.
Recent events (2)
- — I (S) $7760.4
- — Z (S) $12934
1910.212 A01
- Issued
- Sep 19, 2018
- Abate by
- Oct 24, 2018
- Penalty
- Initial $12,934 · Current $7,760 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or about September 5, 2018, employees were utilizing Gantry Drills (#2, #3, #4) to make boxes and pallets without the rotating drill bits being guarded. Employees exposed to being struck-by the rotating drill bits.
Recent events (2)
- — I (S) $7760.4
- — Z (S) $12934
1910.303 F02
- Issued
- Sep 19, 2018
- Abate by
- Oct 1, 2018
- Penalty
- Initial $5,543 · Current $3,326 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about September 5, 2018, at the disconnect panel box labeled Gang Rip Saw, HC3, the breakers were not identified to indicate their purpose. Employees gain access to the disconnect box to isolate the energy sources for the Gang Rip Saw under the company's energy control program.
Recent events (2)
- — I (S) $3325.8
- — Z (S) $5543
1910.305 B02 I
- Issued
- Sep 19, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: On or about September 5 2018, near the lift table on Baldor 80 foot Gang Rip saw. The junction box near the table was missing the cover plate for the 110 volt wiring. Employees exposed to the hazard of an electrical shock.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- Sep 19, 2018
- Abate by
- Oct 1, 2018
- Penalty
- Initial $5,543 · Current $3,326 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or about September 5, 2018, on the shop floor, there were two 110 volt pedestal fans that were not grounded. The fans were being operated and were missing the grounding pins. Employees exposed to the hazard of an electrical shock.
Recent events (2)
- — I (S) $3325.8
- — Z (S) $5543
More inspections at FCA LLC
View FCA LLC's full OSHA safety record →
More inspections in this industry (NAICS 321920)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343441085.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.