CARROLLTON, GA —
OSHA Inspection: DIE-TECH INDUSTRIES, INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of DIE-TECH INDUSTRIES, INC. in 102 AUTOMATION DRIVE, CARROLLTON, GA 30117 (NAICS 336370). OSHA activity number 343471264.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DIE-TECH INDUSTRIES, INC.
- Site address
- 102 AUTOMATION DRIVE
- City
- CARROLLTON
- State
- GA
- ZIP
- 30117
- Mailing
- 102 AUTOMATION DRIVE, CARROLLTON, GA 30117
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336370
- Employees
- 250
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.37 A03
- Issued
- Feb 25, 2019
- Penalty
- Initial $5,115 · Current $5,115
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: (a) Maintenance Building, Exit door located between two roll-up doors: On or about 09/17/2018, and at times prior, the emergency exit door was obstructed and not kept clear in the event of an emergency, in that 55 gallon drums, propane tanks and a pressure washer were placed in front of the door.
Recent events (1)
- — Z (S) $5115
1910.110 F02 II
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.110(f)(2)(ii): Containers when stored inside were located near exits, stairways, or in areas normally used or intended for the safe exit of people. (a) Maintenance Building, Exit door located between two roll-up doors: On or about 09/17/2018, and at times prior, empty forklift propane tanks were stored near the exit, in that the tank created a trip hazard and was not stored in designated areas.
Recent events (1)
- — Z (S) $0
1910.110 E04 III
- Issued
- Feb 25, 2019
- Penalty
- Initial $5,115 · Current $5,115
General-duty citation text
29 CFR 1910.110(e)(4)(iii): Permanent and removable fuel containers were not securely mounted to prevent jarring loose, slipping, or rotating: (a) Production Department, Bay #1: On or about 09/17/2018, and at times prior, employees were exposed to struck-by hazards while operating a powered industrial truck, in that the strap used to hold the propane tank in place was not secured while the truck was being operated throughout the plant. (b) Maintenance Building, Outside Roll-up Door: On or about 09/17/2018, and at times prior, employees were exposed to struck-by hazards while powered industrial truck was used in the yard, in that the propane tank was not secured to the propane tank holder on the truck used outside the plant.
Recent events (1)
- — Z (S) $5115
1910.217 D09 I
- Issued
- Feb 25, 2019
- Penalty
- Initial $13,260 · Current $13,260
General-duty citation text
29 CFR 1910.217(d)(9)(i): The employer did not establish a die setting procedure for mechanical power press(es) that would ensure compliance with 29 CFR 1910.217(c): or in the alternative; Section 5(a)(1) of the OSHA Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees, in that employees were exposed to struck-by hazards: a) Bay #1, Mechanical Press 43: On 09/17/2018, employees were exposed to struck-by hazards while repositioning the die set on the Niagra Mechanical Power Press P-43, in that the bolt/clamps were not all attached and checked prior to raising the die assembly.
Recent events (1)
- — Z (S) $13260
1910.37 B05
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet): (a) Production Department, Bay #3: On or about 09/17/2018, and at times prior, the employer failed to label one of the storage closet doors, in that the closet door was not labeled "Not an exit".
Recent events (1)
- — Z (O) $0
1910.37 B06
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: (a) Die maintenance area, fire exit. On or about 10/17/2018. The employer failed to provide illuminated exit signs in the event of a power outage or fire emergency in the maintenance area.
Recent events (1)
- — Z (O) $0
More inspections at Die-Tech Industries, INC.
View Die-Tech Industries, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 336370)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343471264.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.