Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MACO MANUFACTURING, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MACO MANUFACTURING, INC. in 2204 NORTH GENERAL BRUCE DR., TEMPLE, TX 76504 (NAICS 337214). OSHA activity number 343680161.

Watch Maco Manufacturing, INC. — free Get an email when a new federal OSHA severe-injury report for Maco Manufacturing, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2204 NORTH GENERAL BRUCE DR.
City
TEMPLE
State
TX
ZIP
76504
Mailing
2204 NORTH GENERAL BRUCE DR., TEMPLE, TX 76504
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337214
Employees
30
Ownership type
A

9 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 1 instance 20 exposed
Issued
Apr 9, 2019
Abate by
Apr 15, 2019
Penalty
Initial $5,304 · Current $3,182 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, and service rooms were not kept clean and orderly and in a sanitary condition.  On or about December 12, 2018, and in times prior thereto, the employer did not ensure that all surfaces were kept free of hazardous accumulations of combustible and explosive sawdust, exposing employees to the hazard of fire, deflagration and dust explosion in the mill area.
Recent events (2)
  • — I (S) $3182.4
  • — Z (S) $5304

1910.106 E02 II B 2

Serious Gravity 5 1 instance 30 exposed
Issued
Apr 9, 2019
Penalty
Initial $6,630 · Current $3,978 Reduced
29 CFR 1910.106(e)(2)(ii)(b)(2): More than 120 gallons of Category 2, 3, or 4 flammable or combustible liquids in containers were located outside of inside storage room(s) or storage cabinet(s):  On or about December 12, 2018, and in times prior thereto, approximately 800 gallons of flammable paints, adhesives and thinners were stored in the finishing area creating a fire hazard to painters.
Recent events (2)
  • — I (S) $3978
  • — Z (S) $6630

1910.106 E02 IV D

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 9, 2019
Abate by
Apr 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(2)(iv)(d): Flammable liquids were not drawn from or transferred into vessels, containers, or portable tanks within a building only through a closed piping system, from safety cans, by means of a device drawing through the top, or from a container or portable tanks by gravity through an approved self-closing valve:  On or about December 12, 2018, and in times prior thereto, open drums and buckets were used to transfer flammable paints, thinners and adhesives, located in the flatline/finishing area, exposing workers to a fire hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 D01 III

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 9, 2019
Penalty
Initial $3,978 · Current $2,387 Reduced
29 CFR 1910.134(d)(1)(iii): The employer did not identify and evaluate the respiratory hazard(s) in the workplace; the evaluation did not include a reasonable estimate of employee exposures to respiratory hazard(s) and an identification of the contaminant's chemical state and physical form. Where the employer cannot identify or reasonably estimate the employee exposure, the employer shall consider the atmosphere to be IDLH.  On or about December 12, 2018, and in times prior thereto, the employer did not evaluate the workplace for respiratory hazards related to the exposure of organic vapors, exposing employees to health hazards such as but not limited to inhalation, located in the painting area.
Recent events (2)
  • — I (S) $2386.8
  • — Z (S) $3978

1910.134 G01 I A

Serious Gravity 1 1 instance 1 exposed
Issued
Apr 9, 2019
Abate by
Apr 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.134(g)(1)(i)(A): Respirators with tight-fitting facepieces were worn by employees who had facial hair that came between the sealing surface of the facepiece and the face or that interfered with valve function:  On or about December 12, 2018, and in times prior thereto, employees wearing tight-fitting respirators while performing painting operations were not clean shaven, exposing them to health hazards such as, but not limited to inhalation, located in the painting area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 D01

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 9, 2019
Penalty
Initial $3,978 · Current $2,387 Reduced
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):  On or about December 12, 2018, and in times prior thereto, pulleys on a Speedaire, air compressor were not guarded, exposing workers to a caught in hazard, located in the assembly area.
Recent events (2)
  • — I (S) $2386.8
  • — Z (S) $3978

1910.304 G05

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 9, 2019
Penalty
Initial $5,304 · Current $3,182 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  On or about December 12, 2018, and in times prior thereto, the extension cords energizing a Central Machinery dust collector had missing ground prongs, exposing employees working in the milling area to the hazard of electric shock.
Recent events (2)
  • — I (S) $3182.4
  • — Z (S) $5304

1910.305 B01 II

Serious Gravity 5 2 instances 3 exposed
Issued
Apr 9, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  On or about December 12, 2018, knock-out openings on breaker panels and light switch covers were not provided in the assembly area creating an electric shock hazard to employees.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.307 C

Serious Gravity 5 1 instance 30 exposed
Issued
Apr 9, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:  On or about December 12, 2018, and in times prior thereto, non-intrinsically safe equipment such as, but not limited to electrical panels and receptacles were being used in an area of the facility that was found to have combustible dust, exposing employees to a fire hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Maco Manufacturing, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343680161.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.