Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: TANMAR COMPANIES, LLC

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of TANMAR COMPANIES, LLC in WALER STATE UNIT4 LEASE, WELL 3WA, CACTUS DRILLING RIG #139, 16.74 MILES SE FROM PECOS., PECOS, TX 79772 (NAICS 532490). OSHA activity number 343847364.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tanmar Companies, LLC for free Get an email when a new federal OSHA severe-injury report for Tanmar Companies, LLC is published. One employer, no account, unsubscribe in one click.
Site address
WALER STATE UNIT4 LEASE, WELL 3WA, CACTUS DRILLING RIG #139, 16.74 MILES SE FROM PECOS.
City
PECOS
State
TX
ZIP
79772
Mailing
711 S CHESTNUT ST., TOMBALL, TX 77375
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
532490
Employees
423
Ownership type
Private (A)

6 citations on file for this inspection.

1910.305 B01 I

Repeat 2 instances 2 exposed
Issued
Aug 15, 2019
Abate by
Aug 21, 2019
Penalty
Initial $2,085 · Current $1,251 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed:  On or about February 27, 2019, employees engaged in drilling operations were exposed to electrical shock hazards due to the electrical cord not being protected when run through the breaker box opening in the following instances.  a. Trailer #MH 0514:  DC Solids Control living quarters.  b. Trailer #CCT-030: Cooling Trailer.    TanMar Companies, LLC was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 1185854, citation number 01, item number 001 and was affirmed as a final order on January 31, 2017, with respect to a workplace located at Longfellow Unit 3 Lease, Well 701H, Scan-Producer Drilling Rig.
Recent events (2)
  • · I (R) $1251
  • · Z (R) $2085

1910.305 B01 II

Repeat 1 instance 4 exposed
Issued
Aug 15, 2019
Abate by
Aug 21, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  On or about February 27, 2019, employees engaged in drilling operations were exposed to electrical shock hazards due to an unused opening under breaker box located on trailer #0475 (Directional Driller's quarters).    TanMar Companies, LLC was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 1185854, citation number 01, item number 001 and was affirmed as a final order on January 31, 2017, with respect to a workplace located at Longfellow Unit 3 Lease, Well 701H, Scan-Producer Drilling Rig.
Recent events (2)
  • · I (R) $0
  • · Z (R) $0

1910.303 G02 I

Other-than-serious 1 instance 1 exposed
Issued
Aug 15, 2019
Abate by
Aug 21, 2019
Penalty
Initial $1,169 · Current $701 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:  On or about February 27, 2019, employees engaged in drilling operations were exposed to electrical shock hazards on trailer # MH-0357 (Mud Engineers trailer) since the employer failed to have an electrician reattach a front cover to an AC unit voltage panel which exposed live electrical parts to employee contact.
Recent events (2)
  • · I (O) $701.4
  • · Z (O) $1169

1910.305 B02 I

Other-than-serious 2 instances 5 exposed
Issued
Aug 15, 2019
Abate by
Aug 21, 2019
Penalty
Initial $1,169 · Current $701 Reduced
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   On or about February 27, 2019, employees engaged in drilling operations were exposed to electrical hazards due to the outlet missing the water proof cover in the following instances:  a)    Trailer #MH-0475:- Directional Driller living quarters.     b)    Trailer #MH-0357: Mud Engineer living quarters.
Recent events (2)
  • · I (O) $701.4
  • · Z (O) $1169

1910.305 G01 IV C

Other-than-serious 1 instance 6 exposed
Issued
Aug 15, 2019
Abate by
Aug 21, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were used where run through doorways, windows, or similar openings.  On or about February 27, 2019, employees engaged in drilling operations were exposed to electrical shock hazards due to an extension cord being pinched when run through trailer #020131375 (bathroom trailer) window.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 G02 III

Other-than-serious 3 instances 6 exposed
Issued
Aug 15, 2019
Abate by
Aug 21, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent tension from being directly transmitted to joints or terminal screws:   On or about February 27, 2019, employees engaged in drilling operations were exposed to electrical shock hazards due to electrical breaker boxes having damaged and/or loose strain reliefs in the following instances:  a)    Trailer #MH-0475: Directional Driller living quarter.    b)    Trailer #MH-78483: Water Purifier (8/4 flexible cord with watertight connection has loose strain relief at transformer).    c)    Trailer #MH- 0650: Site Manager living quarter.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0