1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: FAA-ST THOMAS ATCT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FAA-ST THOMAS ATCT in 1 JOHN BREWERS BAY, ST THOMAS, VI 00802 (NAICS 488111). OSHA activity number 344126776.

Watch Faa-St Thomas Atct — free Get an email when a new federal OSHA severe-injury report for Faa-St Thomas Atct is published. One employer, no account, unsubscribe in one click.
Establishment
FAA-ST THOMAS ATCT
Site address
1 JOHN BREWERS BAY
City
ST THOMAS
State
VI
ZIP
00802
Mailing
5000 CARR 190, CAROLINA, PR 00979
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488111
Employees
13
Ownership type
D

3 citations on file for this inspection.

1910.303 G01

Serious Gravity 1 3 instances 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment.  a. On or about 06/25/2019, at Communications Room #110 of the FAA Saint Thomas Air Traffic Control Tower, the electrical service panel in the area was not readily accessible. The electrical service panel was blocked with several boxes, devices and materials stored in the floor below and in front, obstructing access.  b. On or about 06/25/2019, at the Emergency Generator Room of the FAA Saint Thomas Air Traffic Control Tower, the electrical transfer switch panel in the area was not readily accessible. The panel was blocked with various items, including an electrical welding machine, a folding chair, and a  plastic five gallons drinking water cooler stored in the floor below and in front, obstructing access.  c. On or about 06/25/2019, at the Emergency Generator Room of the FAA Saint Thomas Air Traffic Control Tower, the electrical service disconnect panel in the area was not readily accessible. The panel was blocked with a 20 gallons galvanized steel round trash can and  one 14 inches steel round step stool in the floor below and in front, obstructing access.   NOTE: Certification of abatement is not required for this citation item as abatement was witnessed by the compliance safety and health officer during the inspection.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV

Other-than-serious 3 instances 13 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv): Flexible cords and/or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv).  a. On or about 06/25/2019, at the Administrative Area of the FAA Saint Thomas Air Traffic Control Tower, employees were exposed to electrical hazards while using flexible cords and/or cables as a substitute for the fixed wiring of a structure and running through holes in the ceiling and walls.  b. On or about 06/25/2019, at Communications Room #110 of the FAA Saint Thomas Air Traffic Control Tower, employees were exposed to electrical hazards while using flexible cords and/or cables as a substitute for the fixed wiring of a structure while attached to building surface.  c. On or about 06/25/2019, at the Network Servers Room of the FAA Saint Thomas Air Traffic Control Tower, employees were exposed to electrical hazards while using flexible cords and/or cables as a substitute for the fixed wiring of a structure and running through holes in the ceiling.  Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (1)
  • — Z (O) $0

1910.305 B02 I

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.  a. On or about 06/25/2019, at the Network Servers Room of the FAA Saint Thomas Air Traffic Control Tower, employees were exposed to electrical hazards from an electrical junction box with missing cover and fittings.  Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (1)
  • — Z (O) $0

View FAA-ST THOMAS ATCT's full OSHA safety record →