ST THOMAS, VI —
OSHA Inspection: FAA-ST THOMAS ATCT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FAA-ST THOMAS ATCT in 1 JOHN BREWERS BAY, ST THOMAS, VI 00802 (NAICS 488111). OSHA activity number 344126776.
Where did this inspection happen?
- Establishment
- FAA-ST THOMAS ATCT
- Site address
- 1 JOHN BREWERS BAY
- City
- ST THOMAS
- State
- VI
- ZIP
- 00802
- Mailing
- 5000 CARR 190, CAROLINA, PR 00979
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 488111
- Employees
- 13
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.303 G01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment. a. On or about 06/25/2019, at Communications Room #110 of the FAA Saint Thomas Air Traffic Control Tower, the electrical service panel in the area was not readily accessible. The electrical service panel was blocked with several boxes, devices and materials stored in the floor below and in front, obstructing access. b. On or about 06/25/2019, at the Emergency Generator Room of the FAA Saint Thomas Air Traffic Control Tower, the electrical transfer switch panel in the area was not readily accessible. The panel was blocked with various items, including an electrical welding machine, a folding chair, and a plastic five gallons drinking water cooler stored in the floor below and in front, obstructing access. c. On or about 06/25/2019, at the Emergency Generator Room of the FAA Saint Thomas Air Traffic Control Tower, the electrical service disconnect panel in the area was not readily accessible. The panel was blocked with a 20 gallons galvanized steel round trash can and one 14 inches steel round step stool in the floor below and in front, obstructing access. NOTE: Certification of abatement is not required for this citation item as abatement was witnessed by the compliance safety and health officer during the inspection.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv). a. On or about 06/25/2019, at the Administrative Area of the FAA Saint Thomas Air Traffic Control Tower, employees were exposed to electrical hazards while using flexible cords and/or cables as a substitute for the fixed wiring of a structure and running through holes in the ceiling and walls. b. On or about 06/25/2019, at Communications Room #110 of the FAA Saint Thomas Air Traffic Control Tower, employees were exposed to electrical hazards while using flexible cords and/or cables as a substitute for the fixed wiring of a structure while attached to building surface. c. On or about 06/25/2019, at the Network Servers Room of the FAA Saint Thomas Air Traffic Control Tower, employees were exposed to electrical hazards while using flexible cords and/or cables as a substitute for the fixed wiring of a structure and running through holes in the ceiling. Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (1)
- — Z (O) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose. a. On or about 06/25/2019, at the Network Servers Room of the FAA Saint Thomas Air Traffic Control Tower, employees were exposed to electrical hazards from an electrical junction box with missing cover and fittings. Note: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (1)
- — Z (O) $0
More inspections at FAA-ST THOMAS ATCT
ST THOMAS, VI—2025-12-19
FAA-ST THOMAS ATCT
ST THOMAS, VI—2023-05-18 00:00:00
FAA-ST THOMAS ATCT
View FAA-ST THOMAS ATCT's full OSHA safety record →
More inspections in this industry (NAICS 488111)
ANCHORAGE, AK—2026-01-27
DEPT. OF TRANSPORTATION - FAA
ST THOMAS, VI—2025-12-19
FAA-ST THOMAS ATCT
KINGSHILL, VI—2025-12-11
ROBINSON AVIATION INC
MATHER, CA—2025-11-11
ROBINSON AVIATION, INC.
DETROIT, MI—2025-07-24
WAYNE COUNTY AIRPORT AUTHORITY
More inspections in VI
CHARLOTTE AMALIE, VI—2026-05-26
VIRGIN ISLANDS EMERGENCY MANAGEMENT AGENCY
ST CROIX, VI—2026-05-06
VI DEPARTMENT OF HEALTH
ST CROIX, VI—2026-04-28
GOV. JUAN F. LUIS HOSPITAL
ST CROIX, VI—2026-04-24
GOV. JUAN F. LUIS HOSPITAL
CHRISTIANSTED, VI—2026-04-24
OFFICE OF DISASTER RECOVERY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344126776.