MORRAL, OH —
OSHA Inspection: MORRAL COMPANIES, LLC
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of MORRAL COMPANIES, LLC in 132 POSTLE AVENUE, MORRAL, OH 43337 (NAICS 325311). OSHA activity number 344780556.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MORRAL COMPANIES, LLC
- Site address
- 132 POSTLE AVENUE
- City
- MORRAL
- State
- OH
- ZIP
- 43337
- Mailing
- 132 POSTLE AVENUE, MORRAL, OH 43337
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325311
- Employees
- 30
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.119 E01
- Issued
- Oct 13, 2020
- Abate by
- May 3, 2021
- Penalty
- Initial $8,675 · Current $7,482 Reduced
0170
General-duty citation text
29 CFR 1910.119(e)(1): The employer did not perform an initial process hazard analysis (hazard evaluation) on processes covered by 29 CFR 1910.119: Morral Companies, LLC - Morral, Ohio - Anhydrous Ammonia Liquid Department: On or about June 3, 2020, the employer did not have an initial PHA completed for the PSM-covered process which uses anhydrous ammonia to manufacture liquid fertilizer. Failure to conduct an initial PHA to identify, evaluate and control the hazards of the process could lead to a catastrophic release of anhydrous ammonia and could expose process operators to inhalation and fire hazards.
Recent events (2)
- — I (S) $7482
- — Z (S) $8675
1910.119 O04
- Issued
- Oct 13, 2020
- Abate by
- May 3, 2021
- Penalty
- Initial $8,675 · Current $0 Reduced
0170
General-duty citation text
29 CFR 1910.119(o)(4): The employer did not promptly determine and document an appropriate response to each of the findings of the compliance audit, and document that deficiencies have been corrected: Morral Companies, LLC - Morral, Ohio - Anhydrous Ammonia Liquid Department: On or about June 9, 2020, the employer did not implement a system to document responses and corrective action taken on compliance audit findings related to the use of anhydrous ammonia in fertilizer manufacturing in the Liquid Department. Because the system was not developed, findings related to process safety management elements, such as but not limited to, mechanical integrity were not documented or corrected, including findings related to inspection, testing and maintenance of piping and piping components, such as valves. Piping in anhydrous ammonia service between the anhydrous ammonia storage tanks and the Liquid Department was observed to have surface damage (e.g., chipped paint and external corrosion with rust present). Failure to correct and address identified deficiencies in process safety management elements involving ammonia service can result in an unintended release, resulting in fire and inhalation hazards for process operators in the Liquid Department.
Recent events (2)
- — I (S) $0
- — Z (S) $8675
1910.119 J02
- Issued
- Oct 13, 2020
- Abate by
- May 3, 2021
- Penalty
- Initial $8,675 · Current $7,482 Reduced
0170
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment: Morral Companies, LLC - Morral, Ohio - Anhydrous Ammonia Liquid Department: On or about June 9, 2020, the employer did not establish and implement written procedures for maintaining the on-going integrity of process equipment, such as but not limited to anhydrous ammonia piping and piping components, such as valves, which describe the extent and location of inspection activity, frequency of inspection and testing, and acceptance criteria from applicable piping inspection codes used to determine whether piping remains fit for service. The employer uses anhydrous ammonia in the manufacture of liquid fertilizer products in the Liquid Department. Piping in anhydrous ammonia service between the anhydrous ammonia storage tanks and the Liquid Department was observed to have chipped paint and corrosion. Failure to maintain piping and piping components in ammonia service can result in an unintended release, resulting in fire and inhalation hazards.
Recent events (2)
- — I (S) $7482
- — Z (S) $8675
1910.119 J04 I
- Issued
- Oct 13, 2020
- Abate by
- May 3, 2021
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment: Morral Companies, LLC - Morral, Ohio - Anhydrous Ammonia Liquid Department: On or about June 9, 2020, the employer did not ensure that mechanical integrity inspections and testing was performed on process equipment such as but not limited to visually inspecting metal surfaces of piping and piping components, including valves, used to introduce anhydrous ammonia into the fertilizer mixing operations in the Liquid Department, to determine if piping remained fit for service and thickness testing (e.g. acceptable wall thickness). Piping in anhydrous ammonia service between the anhydrous ammonia storage tanks and the Liquid Department was observed to have surface damage (e.g. chipped paint and external corrosion with some rust present). Failure to inspect, test, and maintain piping and piping components in ammonia service can result in an unintended release, resulting in fire and inhalation hazards to process operators in the Liquid Department.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 G03
- Issued
- Oct 13, 2020
- Abate by
- Jan 4, 2021
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(g)(3): The employer did not ascertain that each employee involved in operating a process has received and understood the training required by this paragraph. The employer did not prepare a record which contains the identity of the employee, the date of training, and the means used to verify that the employee understood the training. Morral Companies, LLC - Morral, Ohio - Anhydrous Ammonia Liquid Department: On or about June 9, 2020, the employer did not ensure that training for operators in the Liquid Department was documented with regards to the dates of training and means used to verify that employees understood the training, which was previously provided by the manufacturer/installer of the process equipment. Failure to have written training documentation showing the status of training for employees may result in employees not being trained on how to respond or prevent ammonia releases in the Liquid Department.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Morral Companies, LLC
View Morral Companies, LLC's full OSHA safety record →
More inspections in this industry (NAICS 325311)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344780556.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.