Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: R. SABEE COMPANY LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of R. SABEE COMPANY LLC in 1718 W 8TH STREET, APPLETON, WI 54914 (NAICS 322291). OSHA activity number 344790191.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch R. Sabee Company LLC — free Get an email when a new federal OSHA severe-injury report for R. Sabee Company LLC is published. One employer, no account, unsubscribe in one click.
Site address
1718 W 8TH STREET
City
APPLETON
State
WI
ZIP
54914
Mailing
1718 W. 8TH STREET, APPLETON, WI 54914
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322291
Employees
160
Ownership type
A

6 citations on file for this inspection.

1910.132 D01

Serious Gravity 5 2 instances 10 exposed
Issued
Dec 3, 2020
Penalty
Initial $8,111 · Current $4,867 Reduced
29 CFR 1910.132(d)(1): The employer shall assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE):   On or about June 15, 2020 the employer had not sufficiently detailed a hazard assessment and documentation for maintenance technician employees performing electrical testing and/or troubleshooting activities to determine electric shock and/or arc flash hazards those employees were potentially exposed to.
Recent events (3)
  • — F (S) $4867
  • — C (S) $8111
  • — Z (S) $8111

1910.335 A01 I

Deleted Serious Gravity 5 1 instance 10 exposed
Issued
Dec 3, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed. Note: Personal protective equipment requirements are contained in subpart I of this part.  On or about June 15, 2020 the employer did not ensure that maintenance technician employees were provided with the proper electrical protective equipment when performing electrical testing on overhead electrical components to protect eyes, face, hands and/or other portions of the body.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 3, 2020
Penalty
Initial $8,111 · Current $0 Reduced
29 CFR 1910.332(b)(1): Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments.  On or about June 15, 2020 the employer did not ensure that employees exposed to live conductors when performing work such as, but not limited to, troubleshooting and voltage testing were trained on procedures for working safely on energized circuits and the proper use of personal protective equipment.
Recent events (3)
  • — F (S) $0
  • — C (S) $8111
  • — Z (S) $8111

1910.333 A

Deleted Serious Gravity 5 1 instance 10 exposed
Issued
Dec 3, 2020
Penalty
Initial $8,111 · Current $0 Reduced
29 CFR 1910.333(a): Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards:  On or about June 15, 2020, the employer did not ensure that employees exposed to live conductors when performing work such as, but not limited to, troubleshooting and voltage testing utilized safety-related work practices to prevent electric shock or other injuries including the use of personal protective equipment.
Recent events (3)
  • — F (S) $0
  • — C (S) $8111
  • — Z (S) $8111

1910.333 C02

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 3, 2020
Penalty
Initial $0 · Current $4,867
29 CFR  1910.333(c)(2): "Work on energized equipment." Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.  On or about June 15, 2020, the employer did not ensure that employees exposed to live conductors when performing work such as, but not limited to, troubleshooting and voltage testing were only qualified person(s) and were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials and insulated tools.
Recent events (3)
  • — F (S) $4867
  • — C (S) $0
  • — Z (S) $0

1910.303 G01 I

Other-than-serious 3 instances 10 exposed
Issued
Dec 3, 2020
Abate by
Dec 17, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized shall comply with the following dimensions, except as required or permitted elsewhere in this subpart:  On or about June 15, 2020 the three electrical disconnect switches in the welding cell were blocked by a welding gas cylinder and welding carts and were not kept clear for immediate access.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

View R. Sabee Company LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344790191.