Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: INDIAN TRADING POST

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of INDIAN TRADING POST in 88740 70TH AVE., THERMAL, CA 92274 (NAICS 424490). OSHA activity number 344964473.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Indian Trading Post — free Get an email when a new federal OSHA severe-injury report for Indian Trading Post is published. One employer, no account, unsubscribe in one click.
Establishment
INDIAN TRADING POST
Site address
88740 70TH AVE.
City
THERMAL
State
CA
ZIP
92274
Mailing
88740 70TH AVE., THERMAL, CA 92274
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424490
Employees
13
Ownership type
A

8 citations on file for this inspection.

1910.101 B

Serious Gravity 5 1 instance 4 exposed
Issued
Dec 9, 2020
Abate by
Dec 21, 2020
Penalty
Initial $3,084 · Current $3,084
29 CFR  1910.101(b):"Compressed gases." The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks shall be in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in Sec. 1910.6. Section 3.3.1 of the CGA Pamphlet P-1-1965 refers to storing cylinders in accordance with CGA and NFPA standards. The CGA Pamplet P-1-1991 Section 3.7.4.1 states that "All compressed gas cylinders in service or in storage shall be secured to prevent from falling."  Indian Trading Post /La Chicanita Market, Inside store: Behind the meat/vegetables display a compressed Helium cylinder was upright and unsecure from displacement.  The cylinder was within a foot of live electrical wires and was used for a coat rack.   Employees were exposed to struck- by and electrical shock hazards.
Recent events (1)
  • — Z (S) $3084

1910.303 B01

Serious Gravity 5 1 instance 4 exposed
Issued
Dec 9, 2020
Abate by
Dec 17, 2020
Penalty
Initial $3,084 · Current $3,084
29 CFR  1910.303(b)(1):Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1):  Indian Trading Post /La Chicanita Market, Inside store: Located at the East wall behind the vegetable/meat display on the floor left of the storage room next to a compressed gas cylinder were exposed to live (having current) electrical wires coiled on the floor.  Employees were exposed to electrical hazard(s).
Recent events (1)
  • — Z (S) $3084

1910.303 B02

Serious Gravity 1 6 instances 15 exposed
Issued
Dec 9, 2020
Abate by
Jan 28, 2021
Penalty
Initial $2,313 · Current $2,313
29 CFR  1910.303(b)(2): Electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  Indian Trading Post/La Chicanita Market, Inside store main room: Along the Northwest isle way multiple freezers and/or coolers were plugged into extension cords. Employee(s) were exposed to electrical hazards.  a) The Aeolus Air Conditioner was plugged into an extension cord then into an outlet located  at the East wall dock entryway.   b) Four Unilever Island freezer(s) running parallel to the Northwest isle way were found to be plugged into extension cords that were run from the ceiling tile to an unknown termination point.   c) Coke machine cooler type fridge was found to be plugged into an extension cord that had been run from the ceiling tile to an unknown termination point.
Recent events (1)
  • — Z (S) $2313

1910.305 G01 IV A

Serious Gravity 5 5 instances 15 exposed
Issued
Dec 9, 2020
Abate by
Jan 28, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Indian Trading Post/La Chicanita Market, Inside store: Temporary extension power cords were used to permanently power refrigerators and coolers. Employees were exposed to electrical hazards.  a) Four Unilever Island freezer(s) running parallel to the Northwest isle way were found to be plugged into extension cords that were run from the appliance up to the ceiling tile to an unknown termination point.   b) Coke machine cooler type fridge Northwest of the market main room was found to be plugged into an extension cord that had been run from the appliance to the ceiling tile to an unknown termination point.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 5 instances 13 exposed
Issued
Dec 9, 2020
Abate by
Jan 28, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(B): Flexible cords and cables may not be used where run through holes in walls, ceilings or floors:   Indian Trading Post/La Chicanita Market, Inside store: Temporary extension power cords were run through ceiling tile(s) and used to permanently power refrigerators and coolers.   a) Four Unilever Island freezer(s) running parallel to the Northwest isle way were found to be plugged into extension cords that were run from the appliance up to the ceiling tile to an unknown termination point.   b) Coke machine cooler type fridge Northwest of the market main room was found to be plugged into an extension cord that had been run from the appliance to the ceiling tile to an unknown termination point.  Employees were exposed to electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 1 4 instances 15 exposed
Issued
Dec 9, 2020
Abate by
Dec 21, 2020
Penalty
Initial $2,313 · Current $2,313
29 CFR  1910.303(g)(1)(ii) The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage.  Indian Trading Post/La Chicanita Market, retail store floors: Employees and venders had placed product and supplies directly in front of multiple electrical panels:    a)  The Northeast electrical panel behind the meat display had a black storage rack of supplies, cleaning supplies, and boxes of water stored on the floor blocking access. b)  The East storage room electrical panel had restock beverages placed on the floor in front blocking access. c)   To the left of the Northwest freezers the electrical panel was blocked by  a trash can, boxes, and beverages blocking access. d)  The West storage room electrical panel was blocked by boxes, black trash bag of supplies, and kitchen equipment blocking access    This condition prevented access and immediate shutdown of a circuit to the panel, particularly in the event of an emergency.  This condition exposed employee(s) to an electrical and/or fire hazard(s).
Recent events (1)
  • — Z (S) $2313

1910.305 B02 I

Serious Gravity 5 10 instances 15 exposed
Issued
Dec 9, 2020
Abate by
Jan 28, 2021
Penalty
Initial $3,084 · Current $3,084
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   Indian Trading Post /La Chicanita Market, Inside store: In the following locations electrical outlet and switch covers were open showing exposed live wiring. Employees in the process of conducting assigned tasks throughout the market would use various light switches and outlets for lighting and electrical needs.  a) Northwest wall left to the managers office the box enclosure was missing exposing live electrical wiring. b) Northeast wall,  metal butcher table two outlets had broken covers exposing live electrical wiring.  c) Southeast Meat cutting room box cover missing behind the sink, box covers missing on the Southeast wall, the South wall and the light switch located on the west wall had a missing cover showing live exposed wiring.  d) Southwest wall had a missing outlet cover with a slush machine plugged into it. e) Southwest wall light switch just left of the coke fridge had a cover missing with exposed wiring. f)  Northwest Storage room light switch and wall box enclosure had missing covers with live exposed wiring.  Employees were exposed to electrical hazards.
Recent events (1)
  • — Z (S) $3084

1910.305 D02

Serious Gravity 5 1 instance 15 exposed
Issued
Dec 9, 2020
Abate by
Jan 6, 2021
Penalty
Initial $3,084 · Current $3,084
29 CFR  1910.305(d)(2):Panel boards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front:  Indian Trading Post/La Chicanita Market, Inside store: The electrical panel located in the Northwest storage room had multiple missing dead fronts exposing the bus bars, breakers, and live unattached wires. Employees accessed the storage room daily to retrieve and store supplies. Employees were exposed to electrical hazards.
Recent events (1)
  • — Z (S) $3084

View Indian Trading Post's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344964473.