Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ANHEUSER-BUSCH, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ANHEUSER-BUSCH, INC. in 775 GELLHORN DRIVE, HOUSTON, TX 77029 (NAICS 312120). OSHA activity number 344996442.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Anheuser-Busch, INC. — free Get an email when a new federal OSHA severe-injury report for Anheuser-Busch, INC. is published. One employer, no account, unsubscribe in one click.
Site address
775 GELLHORN DRIVE
City
HOUSTON
State
TX
ZIP
77029
Mailing
775 GELLHORN DRIVE, HOUSTON, TX 77029
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
312120
Employees
665
Ownership type
A

7 citations on file for this inspection.

1910.119 F01 I D

Serious Gravity 10 1 instance 24 exposed
Issued
Mar 25, 2021
Abate by
Apr 29, 2021
Penalty
Initial $13,653 · Current $13,653

Hazardous substances 0170

29 CFR  1910.119(f)(1)(i)(D):The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in emergency shutdown including the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown was executed in a safe and timely manner.  (a) On or about October 27, 2020 and at times prior thereto, at the Anheuser-Busch Houston Brewery, the employer exposed workers to ammonia chemical hazards when it did not develop and implement written procedures that provide clear instruction for safe emergency isolation of the #3 High Pressure Receiver.
Recent events (3)
  • — F (S) $13653
  • — C (S) $13653
  • — Z (S) $13653

1910.119 F03

Serious Gravity 5 2 instances 24 exposed
Issued
Mar 25, 2021
Abate by
Apr 29, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.119(f)(3):The operating procedures were not reviewed as often as necessary to assure that they reflect current operating practice, including changes that result from changes in process chemicals, technology, and equipment, and changes to facilities.   (a) On or about October 27, 2020 and at times prior thereto, at the Anheuser-Busch Houston Brewery, the employer exposed workers to ammonia chemical hazards when it  did not review the operating procedure for emergency shutdown of equipment  often enough to ensure that it was current and accurate for use to .isolate the #3 High Pressure Receiver.  (b)  On or about October 27, 2020 and at times prior thereto, at the Anheuser-Busch Houston Brewery, the employer exposed workers to ammonia chemical hazards when it  did not review the operating procedure for pumpout of receiver vessels  often enough to ensure that it was current and accurate for pumpout of the  #3 High Pressure Receiver.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 J04 I

Deleted Serious Gravity 10 2 instances 24 exposed
Issued
Mar 25, 2021
Abate by
Apr 29, 2021
Penalty
Initial $13,653 · Current $0 Reduced

Hazardous substances 0170

29 CFR 1910.119(j)(4)(i): Inspections and tests were not performed on process equipment:  (a) On or about October 27, 2020 and at times prior thereto, in the Power House at the Anheuser-Busch Houston Brewery the employer failed to test the final element to trip and shutdown the fired boilers functions when the limit for ammonia concentration is exceeded. This condition  exposed workers to potential fire/explosion and toxic release hazards.  (b) On or about October 27, 2020 and at times prior thereto, in the Power House at the Anheuser-Busch Houston Brewery the employer failed to test the final element to trip the ammonia compressors function when the limit for ammonia concentration is exceeded. This condition  exposed workers to potential fire/explosion and toxic release hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $13653
  • — Z (S) $13653

1910.119 J05

Other-than-serious Gravity 10 3 instances 12 exposed
Issued
Mar 25, 2021
Abate by
Apr 29, 2021
Penalty
Initial $13,653 · Current $13,653

Hazardous substances 0170

29 CFR  1910.119(j)(5):The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) in a safe and timely manner when necessary means where taken to assure safe operation.    (a)On or about October 27, 2020 in the Powerhouse of the Anheuser-Busch Houston Brewery the employer did not correct deficiencies of the inlet valve to the #3 High Pressure Receiver in a timely manner.   (b) On or about October 27, 2020 in the EVAP Deck area on the roof of the Powerhouse of the Anheuser-Busch Houston Brewery the employer did not correct deficiencies in the ammonia piping down comer, piping going to the pump out system and other critical piping to the receivers , in a timely manner.   (c) On or about October 27, 2020 in the EVAP Deck area on the roof of the Powerhouse of the Anheuser-Busch Houston Brewery the employer did not correct deficiencies in electrical and controls system, in that there were broken and open conduit with electrical wires visible inside for the ammonia system in a timely manner.
Recent events (3)
  • — F (O) $13653
  • — C (S) $13653
  • — Z (S) $13653

1910.212 A05

Other-than-serious Gravity 10 1 instance 6 exposed
Issued
Mar 25, 2021
Abate by
Apr 29, 2021
Penalty
Initial $13,653 · Current $13,653
29 CFR  1910.212(a)(5):Fan blade guards, where the periphery of the blades was less than seven feet above the floor or working level, had openings larger than one half inch:  (a) On or about December 11, 2020 and at subsequent times in the EVAP Condenser area on the roof of the Power House at the Anheuser-Busch Houston Brewery, a motor in the circulating water system for the condensers had openings larger than one-half inch in the motor fan guard, exposing workers to hazard of coming into contact with the fan blades.
Recent events (3)
  • — F (O) $13653
  • — C (S) $13653
  • — Z (S) $13653

1910.28 B01 I

Serious Gravity 5 1 instance 12 exposed
Issued
Mar 25, 2021
Penalty
Initial $9,753 · Current $9,753
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that was 4 feet (1.2 m) or more above a lower level was protected from falling by one or more of the following: guardrail systems; safety net systems; or personal fall protection systems, such as personal fall arrest, travel restraint, or positioning systems.  On or about October 27, 2020 in the Power House at the Anheuser-Busch Houston Brewery, employees who work from the work platform above the high pressure receiver vessels were exposed to falls from elevated heights greater than 4 feet; when the employer failed to ensure sections of the guard rail system that were missing was repaired and  or replaced.
Recent events (3)
  • — F (S) $9753
  • — C (S) $9753
  • — Z (S) $9753

1910.305 B01 I

Serious Gravity 5 1 instance 12 exposed
Issued
Mar 25, 2021
Abate by
Apr 29, 2021
Penalty
Initial $7,802 · Current $7,802
29 CFR  1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed.   (a) On or around October 27, 2020 and at times subsequent thereto, in the Evaporative Condenser area on the roof of the Power House of the Anheuser-Busch Houston Brewery, the employer exposed workers to electric shock hazards and possible exposure to hazards associated with ammonia when conductors entering fittings in the control system of the Evaporative Condensers were not protected from abrasion where openings through which the conductors enter were not effectively closed.
Recent events (3)
  • — F (S) $7802
  • — C (S) $7802
  • — Z (S) $7802

View Anheuser-Busch, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344996442.