OSHA Inspection: JM EAGLE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of JM EAGLE in 6500 N BROWN STATION RD, COLUMBIA, MO 65202 (NAICS 326122). OSHA activity number 345012629.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch JM Eagle — free Get an email when a new federal OSHA severe-injury report for JM Eagle is published. One employer, no account, unsubscribe in one click.
Establishment
JM EAGLE
Site address
6500 N BROWN STATION RD
City
COLUMBIA
State
MO
ZIP
65202
Mailing
6500 N BROWN STATION RD, COLUMBIA, MO 65202
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326122
Employees
43
Ownership type
A

4 citations on file for this inspection.

1910.179 G02 I

Serious Gravity 5 1 instance 8 exposed
Issued
Feb 19, 2021
Penalty
Initial $7,802 · Current $4,681 Reduced

Hazardous substances 8870

29 CFR  1910.179(g)(2)(i):Electrical equipment was not so located or enclosed that live parts would not be exposed to accidental contact under normal operating conditions:  At the workplace located at 6500 North Brown Station Road, Columbia, Missouri 65202, Employees were exposed to serious electrical hazards. The crane disconnect electrical panel attached to the Abell-Howe crane was not effectively enclosed. The front panel was open and blocked from closing.
Recent events (2)
  • — I (S) $4681.2
  • — Z (S) $7802

1910.303 B01 IV

Serious Gravity 5 5 instances 8 exposed
Issued
Feb 19, 2021
Penalty
Initial $7,802 · Current $4,681 Reduced

Hazardous substances 8870

29 CFR  1910.303(b)(1)(iv):Electric equipment was not free from recognized hazards that are likely to cause serious physical harm to employees, such as damaged insulation:  At the workplace located at 6500 North Brown Station Road, Columbia, Missouri 65202, employees were exposed to serious electrical hazards. Multiple locations throughout the production floor had damaged electrical insulation, which exposed employees to electrical contact. .   a. South end of production line 3 and hydrostatic tester, opposite of operator station.. b. Southeast side of production line 2, which faces production line 1. c. TEFC A.C. Motor generator, north end of production line 2. d. Electrical panel on east wall by the re-grinder. e. Portable electric fan located by production line 2.
Recent events (2)
  • — I (S) $4681.2
  • — Z (S) $7802

1910.305 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 19, 2021
Penalty
Initial $7,802 · Current $4,681 Reduced

Hazardous substances 8870

29 CFR  1910.305(b)(1)(ii):Unused openings in boxes, cabinets, or fittings were not effectively closed:  At the workplace located at 6500 North Brown Station Road, Columbia, Missouri 65202, employees were exposed to serious electrical hazards. The Cutler-Hammer electrical panel on the east wall by the re-grinder had an unused opening that was not effectively closed. Employees were exposed to 480 volts of electrical current.
Recent events (2)
  • — I (S) $4681.2
  • — Z (S) $7802

1910.305 B02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 19, 2021
Penalty
Initial $7,802 · Current $4,681 Reduced

Hazardous substances 8870

29 CFR  1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:   At the workplace located at 6500 North Brown Station Road, Columbia, Missouri 65202, employees were exposed to serious electrical hazards. employees were exposed to electrical current of 120 to 480 volts.   a. Electrical outlet at the bottom of the re-grinder pit. b. Cutler-Hammer electrical panel on the east wall by the re-grinder. c. Junction box without a cover with exposed wiring next to the Cutler-Hammer electrical panel on the east wall.
Recent events (2)
  • — I (S) $4681.2
  • — Z (S) $7802

View JM Eagle's full OSHA safety record →