OSHA Inspection: COILING TECHNOLOGIES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of COILING TECHNOLOGIES, INC. in 7777 WRIGHT RD., HOUSTON, TX 77041 (NAICS 332613). OSHA activity number 345132526.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Coiling Technologies, INC. — free Get an email when a new federal OSHA severe-injury report for Coiling Technologies, INC. is published. One employer, no account, unsubscribe in one click.
Site address
7777 WRIGHT RD.
City
HOUSTON
State
TX
ZIP
77041
Mailing
7777 WRIGHT RD., HOUSTON, TX 77041
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332613
Employees
62
Ownership type
A

8 citations on file for this inspection.

1910.22 A03

Serious Gravity 1 1 instance 6 exposed
Issued
Apr 6, 2021
Abate by
Apr 16, 2021
Penalty
Initial $4,505 · Current $2,700 Reduced
29 CFR  1910.22(a)(3):The employer did not ensure that walking-working surfaces are maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice.  On or about February 3, 2021, employees near the shot peening machines were exposed to slipping hazards due to shot covering the floor throughout the area.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4505

1910.303 B07 III

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 6, 2021
Abate by
Apr 30, 2021
Penalty
Initial $7,510 · Current $4,575 Reduced
29 CFR  1910.303(b)(7)(iii):Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, were damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues:  On or about February 3, 2021, employees were exposed to electrical and fire hazards when the electrical cabinet for the vertical shot peening machine was contaminated by metal shot.
Recent events (2)
  • — I (S) $4575
  • — Z (S) $7510

1910.303 G02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Apr 6, 2021
Abate by
Apr 30, 2021
Penalty
Initial $7,510 · Current $0 Reduced
29 CFR  1910.303(g)(2)(i):Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  On or about February 3, 2021, employees were exposed to electrical hazards when a shot peen electrical cabinet, that had live parts operating more than 50 volts, had a unapproved hook keeping the cabinet closed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7510

1910.304 F01 IV

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 6, 2021
Abate by
Apr 16, 2021
Penalty
Initial $4,505 · Current $4,575
29 CFR  1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:   On or about February 3, 2021,  employees were exposed to electrical and fire hazards when the space in front of the electrical panel for the Aqua 800 machine was used to stored surplus equipment and was not readily accessible.
Recent events (2)
  • — I (S) $4575
  • — Z (S) $4505

1910.305 B01 II

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 6, 2021
Abate by
Apr 30, 2021
Penalty
Initial $7,510 · Current $0 Reduced
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   On or about January 15, 2021, employees in the heat treat area were exposed to an electrical hazard while working near an electrical panel that had an unused opening without a cover to close that opening.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7510

1910.305 G01 IV A

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 6, 2021
Abate by
Apr 30, 2021
Penalty
Initial $7,510 · Current $4,575 Reduced
29 CFR  1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a.  On or about February 3, 2021, employees in the grinding area were exposed to electrical hazards from a flexible cord which was used as a substitute for fixed wiring to power a table grinder and sander.  b.  On or about February 3, 2021, employees in the shot peening area were exposed to electrical hazards from a flexible cord which was used as a substitute for fixed wiring to power a hoist.
Recent events (2)
  • — I (S) $4575
  • — Z (S) $7510

1910.335 A01 I

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 6, 2021
Abate by
Apr 30, 2021
Penalty
Initial $7,510 · Current $4,575 Reduced
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:   On or about February 3, 2021, employees were exposed to electrical hazards when measuring voltage and amperage on electrical equipment that was approximately 480 volts without being provided arc-rated clothing and heavy-duty gloves.
Recent events (2)
  • — I (S) $4575
  • — Z (S) $7510

5(a)(1)

Repeat Gravity 5 1 instance 4 exposed
Issued
Apr 6, 2021
Abate by
Jun 1, 2021
Penalty
Initial $15,020 · Current $9,000 Reduced
29 CFR OSH ACT of 1970 Section (5)(a)(1):The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to combustible dust explosion, deflagration and fire hazards.   On or about February 3, 2021, employees were exposed to combustible dust explosions, fire and deflagration hazards while performing production and maintenance activities while using the shot peening machine and dust collection system.   Coiling Technologies, Inc. was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 1201514, citation number 1, item number 1 and was affirmed as a final order on June 26, 2017, with respect to a workplace located at 7777 Wright Rd Houston, TX 77041.
Recent events (2)
  • — I (R) $9000
  • — Z (R) $15020

View Coiling Technologies, INC.'s full OSHA safety record →