DELTA, OH —
OSHA Inspection: WORTHINGTON INDUSTRIES
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of WORTHINGTON INDUSTRIES in 6303 COUNTY ROAD 10, DELTA, OH 43515 (NAICS 332813). OSHA activity number 345184766.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WORTHINGTON INDUSTRIES
- Site address
- 6303 COUNTY ROAD 10
- City
- DELTA
- State
- OH
- ZIP
- 43515
- Mailing
- 6303 COUNTY ROAD 10, DELTA, OH 43515
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332813
- Employees
- 205
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.333 B02
- Issued
- Jun 30, 2021
- Abate by
- Jul 19, 2021
- Penalty
- Initial $13,653 · Current $13,653
General-duty citation text
29 CFR 1910.333(b)(2):While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): a.) On or about March 2, 2021 the employer did not ensure the Galv Line electrical cabinet in the MCC Room was deenergized and locked out prior to troubleshooting loose terminals, and were exposed to electric shock and arc flash hazards.
Recent events (2)
- — I (S) $13653
- — Z (S) $13653
1910.333 C02
- Issued
- Jun 30, 2021
- Abate by
- Jul 19, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(c)(2):The employer did not ensure that only qualified persons were allowed to work on energized circuit parts or equipment that had not been de-energized under the procedures of paragraph (b) of this section. A) On or about March 2, 2021, the employer failed to ensure that maintenance employees, who conducted electrical troubleshooting and tightening loose terminals in the Galv Line cabinet in the MCC Room, were qualified to work on electric circuit parts or equipment that have not been deenergized. Employees were exposed to electrical and arc flash hazards associated with 480 volts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Jun 30, 2021
- Abate by
- Jul 19, 2021
- Penalty
- Initial $13,653 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a.) On or about March 9, 2021, the employer did not ensure electricians were protected while performing work on or near 480V circuits. Employees were required to troubleshoot loose connections for the Galv Line electrical cabinet in the MCC Room and did not wear required hand and body protection while performing live electrical work, exposing them to electrical shock and arc flash hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $13653
1910.332 B01
- Issued
- Jun 30, 2021
- Abate by
- Jul 19, 2021
- Penalty
- Initial $13,653 · Current $13,653
General-duty citation text
29 CFR 1910.332(b)(1):Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a.) On or about March 2, 2021, the employer did not ensure employees were familiar with electrical safety related work places before performing work on 480V circuits. Employees were required to troubleshoot loose connections for the Galv Line electrical cabinet in the MCC Room and did not have a full understanding of working with live 480V terminals.
Recent events (2)
- — I (S) $13653
- — Z (S) $13653
More inspections at Worthington Industries
View Worthington Industries's full OSHA safety record →
More inspections in this industry (NAICS 332813)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345184766.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.