Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WORTHINGTON INDUSTRIES

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of WORTHINGTON INDUSTRIES in 6303 COUNTY ROAD 10, DELTA, OH 43515 (NAICS 332813). OSHA activity number 345184766.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Worthington Industries — free Get an email when a new federal OSHA severe-injury report for Worthington Industries is published. One employer, no account, unsubscribe in one click.
Site address
6303 COUNTY ROAD 10
City
DELTA
State
OH
ZIP
43515
Mailing
6303 COUNTY ROAD 10, DELTA, OH 43515
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332813
Employees
205
Ownership type
A

4 citations on file for this inspection.

1910.333 B02

Serious Gravity 10 1 instance 20 exposed
Issued
Jun 30, 2021
Abate by
Jul 19, 2021
Penalty
Initial $13,653 · Current $13,653
29 CFR  1910.333(b)(2):While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2):  a.)	On or about March 2, 2021 the employer did not ensure the Galv Line electrical cabinet in the MCC Room was deenergized and locked out prior to troubleshooting loose terminals, and were exposed to electric shock and arc flash hazards.
Recent events (2)
  • — I (S) $13653
  • — Z (S) $13653

1910.333 C02

Serious Gravity 10 1 instance 20 exposed
Issued
Jun 30, 2021
Abate by
Jul 19, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.333(c)(2):The employer did not ensure that only qualified persons were allowed to work on energized circuit parts or equipment that had not been de-energized under the procedures of paragraph (b) of this section.  A)	On or about March 2, 2021, the employer failed to ensure that maintenance employees, who conducted electrical troubleshooting and tightening loose terminals in the Galv Line cabinet in the MCC Room, were qualified to work on electric circuit parts or equipment that have not been deenergized. Employees were exposed to electrical and arc flash hazards associated with 480 volts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 20 exposed
Issued
Jun 30, 2021
Abate by
Jul 19, 2021
Penalty
Initial $13,653 · Current $0 Reduced
29 CFR  1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a.)	On or about March 9, 2021, the employer did not ensure electricians were protected while performing work on or near 480V circuits. Employees were required to troubleshoot loose connections for the Galv Line electrical cabinet in the MCC Room and did not wear required hand and body protection while performing live electrical work, exposing them to electrical shock and arc flash hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $13653

1910.332 B01

Serious Gravity 10 1 instance 20 exposed
Issued
Jun 30, 2021
Abate by
Jul 19, 2021
Penalty
Initial $13,653 · Current $13,653
29 CFR  1910.332(b)(1):Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  a.)	On or about March 2, 2021, the employer did not ensure employees were familiar with electrical safety related work places before performing work on 480V circuits. Employees were required to troubleshoot loose connections for the Galv Line electrical cabinet in the MCC Room and did not have a full understanding of working with live 480V terminals.
Recent events (2)
  • — I (S) $13653
  • — Z (S) $13653

View Worthington Industries's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345184766.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.