CANTON, GA —
OSHA Inspection: U-TEC CONSTRUCTION, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of U-TEC CONSTRUCTION, INC. in 1 REINHARDT COLLEGE PARKWAY/100 RIVERSTONE TER., CANTON, GA 30114 (NAICS 237130). OSHA activity number 345328611.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U-TEC CONSTRUCTION, INC.
- Site address
- 1 REINHARDT COLLEGE PARKWAY/100 RIVERSTONE TER.
- City
- CANTON
- State
- GA
- ZIP
- 30114
- Mailing
- 926 RIDGEDALE DRIVE, LAWRENCEVILLE, GA 30043
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- Employees
- 515
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.950 B01 I
- Issued
- Nov 22, 2021
- Abate by
- Jan 11, 2022
- Penalty
- Initial $13,653 · Current $0 Reduced
General-duty citation text
29 CFR 1926.950(b)(1)(i):Each employee was not trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this subpart that pertain to his or her job assignments. (a) Site, 1 Reinhardt Parkway/100 Riverstone Terrace, Canton, GA 30114: On or about May 25, 2021 and at times prior to, workers were exposed to thermal radiation burn hazards and amputation hazards, in that the employer did not provide training on the recognition of arc-flash hazards, the associated energies, the minimum approach distances, and the protective equipment for personnel working/standing in proximity of energized parts.
Recent events (3)
- — F (S) $0
- — C (S) $13653
- — Z (S) $13653
1926.952 A02
- Issued
- Nov 22, 2021
- Abate by
- Jan 11, 2022
- Penalty
- Initial $13,653 · Current $10,922 Reduced
General-duty citation text
29 CFR 1926.952(a)(2): Briefing by the employee in charge. The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (b), (c), and (d) of this section with the employees involved before they start each job. (a) Site, 1 Reinhardt College Parkway/100 Riverstone Terrace, Canton, GA 30114; On or about May 25, 2021 employees were exposed to burn hazards, in that the employer did not ensure that a job briefing was conducted before the start of each job performed at the 25 KV/14.4 KV pad-mount switchgear, identified with internal label GG6354.
Recent events (3)
- — F (O) $10922
- — C (S) $13653
- — Z (S) $13653
1926.960 C01 III
- Issued
- Nov 22, 2021
- Abate by
- Jan 4, 2022
- Penalty
- Initial $13,653 · Current $10,922 Reduced
General-duty citation text
29 CFR 1926.960(c)(1)(iii): The employer did not ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless the measures outlined in 1926.960(c)(1)(iii)(A) - (C) were met: (a) Site, 1 Reinhardt College Parkway/100 Riverstone Terrace, Canton, GA 30114; On or about May 25, 2021 and at times prior to, employees were exposed to burn hazards in that the employer did not ensure that minimum approach distances (MADs) for personnel and conductive objects were observed during work performed at the 25 KV/15 KV energized pad-mount switchgear GG6354.
Recent events (3)
- — F (O) $10922
- — C (S) $13653
- — Z (S) $13653
1926.960 G04
- Issued
- Nov 22, 2021
- Abate by
- Jan 4, 2022
- Penalty
- Initial $13,653 · Current $10,922 Reduced
General-duty citation text
29 CFR 1926.960(g)(4):Flame-resistant clothing. The employer did not ensure that the outer layer of clothing worn by an employee, except for clothing not required to be arc rated under paragraphs (g)(5)(i) through (g)(5)(v) of this section, was flame resistant under any of the conditions specified under paragraphs g(4)(i) through g(4)(iii) of this section:. (a) Site, 1Reinhardt College Parkway/100 Riverstone Terrace, Canton, GA 30114; On or about May 25, 2021 employees were exposed to burn hazards in that the employer did not ensure that flame resistant clothing was in use while in proximity of work performed on energized parts.
Recent events (3)
- — F (O) $10922
- — C (S) $13653
- — Z (S) $13653
More inspections at U-Tec Construction, INC.
View U-Tec Construction, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 237130)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345328611.