SAIPAN, MP —
OSHA Inspection: L&T GROUP OF COMPANIES, LTD
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of L&T GROUP OF COMPANIES, LTD in REM CENTER GUALO RAI, SAIPAN, MP 96950 (NAICS 561320). OSHA activity number 345388615.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- L&T GROUP OF COMPANIES, LTD
- Site address
- REM CENTER GUALO RAI
- City
- SAIPAN
- State
- MP
- ZIP
- 96950
- Mailing
- P.O. BOX 501280, SAIPAN, MP 96950
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561320
- Employees
- 116
- Ownership type
- A
Citations
6 citations on file for this inspection.
1926.403 B02
- Issued
- Sep 23, 2021
- Abate by
- Oct 13, 2021
- Penalty
- Initial $5,266 · Current $3,686 Reduced
General-duty citation text
29 CFR 1926.403(b)(2):Listed, labeled or certified equipment was not installed and used in accordance with instructions in the listing, labeling or certification. In the middle of the floor: An extension cord with a receptacle box designed to be installed on a wall was used to provide power to a Makita chipper used to demolish the cement wall. Employees were exposed to fire and electrical hazards.
Recent events (2)
- — I (S) $3686.2
- — Z (S) $5266
1926.405 G02 IV
- Issued
- Sep 23, 2021
- Abate by
- Oct 13, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws: Middle of room: An electrical cord with the outer insulation pulled back from the plug was used to power a Makita chipper, exposing employees to fire and electrical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.405 G02 III
- Issued
- Sep 23, 2021
- Abate by
- Oct 13, 2021
- Penalty
- Initial $5,266 · Current $3,686 Reduced
General-duty citation text
29 CFR 1926.405(g)(2)(iii): Flexible cords were not used only in continuous lengths without splice or tap: a. Walkway across from the room being demolished: A spliced electrical cord was used to power a Makita chipper, exposing employees to fire and electrical hazards. b. Back Wall: Spliced cords were used to power temporary lights, exposing employees to fire and electrical hazards. c. Middle of ceiling: Spliced cords were used to power temporary lights, exposing employees to fire and electrical hazards.
Recent events (2)
- — I (S) $3686.2
- — Z (S) $5266
1910.1200 G08
- Issued
- Sep 23, 2021
- Abate by
- Sep 30, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work shift to employees when they were in their work area. The safety data sheet for the paint being used was not available on the jobsite. Employees were exposed to chemical hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1926.405 A02 II E
- Issued
- Sep 23, 2021
- Abate by
- Oct 13, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(E):Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage. Back wall of room: Temporary lights used for illumination were not protected from breakage, exposing employees to laceration hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1926.405 A02 II F
- Issued
- Sep 23, 2021
- Abate by
- Oct 13, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(F):Temporary lights were suspended by their electric cords and were not designed for this means of suspension: a. Back of the room: The temporary lighting string was suspended along the wall from the electrical cord by metal wire. Employees were exposed to electrical hazards. b. Middle of ceiling: The temporary lighting string was suspended overhead from the electrical cord by metal wire. Employees were exposed to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at L&T Group of Companies, LTD
View L&T Group of Companies, LTD's full OSHA safety record →
More inspections in this industry (NAICS 561320)
More inspections in MP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345388615.