Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MASSACHUSETTS ELECTRIC COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of MASSACHUSETTS ELECTRIC COMPANY in 35 WILLARD ST, GRAFTON, MA 01519 (NAICS 221118). OSHA activity number 345489041.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Massachusetts Electric Company — free Get an email when a new federal OSHA severe-injury report for Massachusetts Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
35 WILLARD ST
City
GRAFTON
State
MA
ZIP
01519
Mailing
40 SYLVAN RD., WALTHAM, MA 02451
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221118
Employees
5
Ownership type
A

2 citations on file for this inspection.

1910.269 A02 II

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Dec 7, 2021
Abate by
Jan 19, 2022
Penalty
Initial $13,653 · Current $0 Reduced
29 CFR  1910.269(a)(2)(ii) : Qualified Employee Training;  Each qualified employee was not trained and competent in sections 1910.269(a)(2)(ii)(A) through 1910.269(a)(2)(ii)(E):   Jobsite -35 Willard St. Grafton, MA. Pole 15   On or about 08/20/2021,  the employer did not ensure that each electrically qualified employee was trained in, competent in and have the  skills and techniques necessary to determine the nominal voltage of exposed live parts, the minimum approach distances specified in this subpart corresponding to the voltages to which the qualified employee will be exposed and the skills and techniques necessary to maintain those distances, the proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electric equipment, and the recognition of electrical hazards to which the employee may be exposed and the skills and techniques necessary to control or avoid these hazards. Specifically, on  08/20/2021 employees installing a low side cutout lead  to the conductor on the road side phase  were not aware of how to  suffiently cover the exposed live equipment with adequate lengths  of protective line hoses and blankets prior to comencing with making  low side connections.  Additionally,  the employees did not position themseves  on the outside of  the roadside line to minize the arc flash potential posed by the center phase line.      Specific abatement documentation that this violation has been corrected must be provided within 10 days of the abatement in accordance with 29CFR1903.19(d)(1).
Recent events (2)
  • — I (S) $0
  • — Z (S) $13653

1910.269 L05 I

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 7, 2021
Abate by
Jan 4, 2022
Penalty
Initial $13,653 · Current $6,827 Reduced
29 CFR  1910.269(l)(5)(i):The employer did not ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, un-insulated parts energized at a potential different from the employee's.  a) 35 Willard St. Grafton, MA. Pole 15: On or about 08/20/2021, an employee was in the process of installing solid blades disconnects to tie two separte feeders tpgether. The employee positioned himself  between the center and road side phase in order to install a cut out when a flash occured. The employer did not effectively ensure that the employee sufficiently recognized the need to position himself outside of the phases to minimize the arc flash potential.      Specific abatement documentation that this violation has been corrected must be provided within 10 days of the abatement in accordance with 29CFR1903.19(d)(1).
Recent events (2)
  • — I (S) $6826.5
  • — Z (S) $13653

View Massachusetts Electric Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345489041.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.