Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MASSACHUSETTS ELECTRIC COMPANY

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of MASSACHUSETTS ELECTRIC COMPANY in 500 SALEM STREET, MEDFORD, MA 02155 (NAICS 221122). OSHA activity number 345982011.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Massachusetts Electric Company — free Get an email when a new federal OSHA severe-injury report for Massachusetts Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
500 SALEM STREET
City
MEDFORD
State
MA
ZIP
02155
Mailing
40 SYLVAN ROAD, WALTHAM, MA 02451
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
17000
Ownership type
A

5 citations on file for this inspection.

1910.269 C02

Serious Gravity 10 1 instance 6 exposed
Issued
Nov 17, 2022
Abate by
May 16, 2023
Penalty
Initial $14,502 · Current $14,502
29 CFR  1910.269(c)(2): The job briefing did not cover at least the following subjects:  hazards associated with the job, work procedures involved, special precautions, energy-source controls, and personal protective equipment requirements.  (a) Location - 500 Salem Street, Medford, MA  On or about 05/26/2022, an employee was exposed to electrical hazards, whereas a job brief was completed but did not address working in an energized transformer.
Recent events (2)
  • — I (S) $14502
  • — Z (S) $14502

1910.269 L03 III

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 17, 2022
Penalty
Initial $14,502 · Current $14,502
29 CFR  1910.269(l)(3)(iii): The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless:  [A] The employee is insulated from the energized part (rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (l)(4) of this section constitutes insulation of the employee from the energized part upon which the employee is working provided that the employee has control of the part in a manner sufficient to prevent exposure to uninsulated portions of the employee's body), or  [B] The energized part is insulated from the employee and from any other conductive object at a different potential, or  [C] The employee is insulated from any other exposed conductive object in accordance with the requirements for live-line bare hand work in paragraph (q)(3) of this section.  (a) Location - 500 Salem Street, Medford, MA  On or about 05/26/2022, an employee was exposed to live electrical components in a transformer that was not insulated to protect the employee from electrocution.
Recent events (2)
  • — I (S) $14502
  • — Z (S) $14502

1910.269 L05 I

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 17, 2022
Penalty
Initial $14,502 · Current $0 Reduced
29 CFR  1910.269(l)(5)(i): The employer did not ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, un-insulated parts energized at a potential different from the employee's.  (a) Location - 500 Salem Street, Medford, MA  On or about 05/26/2022, employees were not protected from shock while working in a transformer that was being back-fed by a generator.
Recent events (2)
  • — I (S) $0
  • — Z (S) $14502

1910.269 M03 II

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 17, 2022
Penalty
Initial $14,502 · Current $0 Reduced
29 CFR  1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy might be supplied to the particular lines and equipment were de-energized / inoperable (i.e. open) and then did not ensure that such means were tagged to indicate that employees were at work.  (a) Location - 500 Salem Street, Medford, MA  On or about 05/26/2022, an employee was not protected from a known energized electrical source.
Recent events (2)
  • — I (S) $0
  • — Z (S) $14502

1910.269 W07

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 17, 2022
Penalty
Initial $14,502 · Current $14,502
29 CFR  1910.269(w)(7): Backfeed. When there is a possibility of voltage backfeed from sources of cogeneration or from the secondary system (for example, backfeed from more than one energized phase feeding a common load), the employer shall ensure requirements of paragraph (l) of this section are applied if employees will work the lines or equipment as energized, and the requirements of paragraphs (m) and (n) of this section are applied if employees will work the lines or equipment as deenergized.  (a) Location - 500 Salem Street, Medford, MA  On or about 05/26/2022, employees were not protected from an energized transformer that was being back-fed from a generator.
Recent events (2)
  • — I (S) $14502
  • — Z (S) $14502

View Massachusetts Electric Company's full OSHA safety record →