HOUSTON, TX —
OSHA Inspection: ASC ENGINEERED SOLUTIONS, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ASC ENGINEERED SOLUTIONS, LLC in 6618 NAVIGATION BLVD, HOUSTON, TX 77011 (NAICS 332996). OSHA activity number 345519763.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ASC ENGINEERED SOLUTIONS, LLC
- Site address
- 6618 NAVIGATION BLVD
- City
- HOUSTON
- State
- TX
- ZIP
- 77011
- Mailing
- 6618 NAVIGATION BLVD, HOUSTON, TX 77011
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332996
- Employees
- 32
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.303 G01 I B
- Issued
- Oct 18, 2021
- Penalty
- Initial $4,973 · Current $2,984 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : a) At building #7, the width of the working space in front of the electrical power switches were less than 30 inches, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $2984
- — Z (S) $4973
1910.305 B01 II
- Issued
- Oct 18, 2021
- Penalty
- Initial $4,973 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) At building #7, an unused opening to an electrical panel box was not effectively closed, exposing employees to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (S) $4973
1910.305 G02 III
- Issued
- Oct 18, 2021
- Penalty
- Initial $4,973 · Current $2,984 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) At the stencil department, strain relief was not provided to an electrical cable of a control pendant, exposing employees to electrical hazards. b) At the Takisawa building, strain relief was not provided to an electrical cord of a fan, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $2984
- — Z (S) $4973
1910.147 C06 I
- Issued
- Oct 18, 2021
- Abate by
- Nov 12, 2021
- Penalty
- Initial $931 · Current $559 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: a) The employer did not conduct a periodic inspection of the energy control procedure for a Takisawa CNC machine, model #TT200, serial #TNRW4199, exposing employees to amputation hazards.
Recent events (2)
- — I (O) $559
- — Z (O) $931
More inspections at ASC Engineered Solutions, LLC
View ASC Engineered Solutions, LLC's full OSHA safety record →
More inspections in this industry (NAICS 332996)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345519763.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.