Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LSC COMMUNICATIONS

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of LSC COMMUNICATIONS in 830 MIDWAY ROAD, MENASHA, WI 54952 (NAICS 323117). OSHA activity number 345811749.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch LSC Communications — free Get an email when a new federal OSHA severe-injury report for LSC Communications is published. One employer, no account, unsubscribe in one click.
Establishment
LSC COMMUNICATIONS
Site address
830 MIDWAY ROAD
City
MENASHA
State
WI
ZIP
54952
Mailing
PO BOX 60, MENASHA, WI 54952
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323117
Employees
360
Ownership type
A

1 citation on file for this inspection.

1910.303 G01 III

Other-than-serious 4 instances 8 exposed
Issued
Apr 29, 2022
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(iii): At least one entrance of sufficient area shall be provided to give access to the working space about electric equipment.  On or about March 2, 2022, electrical disconnecting switches and switching devices were not provided with sufficient area to give access to the working space of electrical equipment.  Specifically:  a.  The electrical disconnecting switch labeled "Item # P03004, Belt #2450 or 4L450", located in the Jeep Shop, was not provided with sufficient area for accessing the working space.  b.  The switching device (circuit breaker) panels 106 and 108, located at the Punch Station, was not provided with sufficient area for accessing the working space.  c.  The electrical disconnecting switch labeled "Switch For Automatic Punches Only Not Hand Punches", located at the Punch Station, was not provided with sufficient room to access the working space.  d.  The switching device (circuit breaker) panel labeled "126 BRKR 19-23", located in the East Docks, was not provided with sufficient area for accessing the working space.
Recent events (1)
  • — Z (O) $0

View LSC Communications's full OSHA safety record →