Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. BORDER PATROL- YUMA SECTOR

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of U.S. BORDER PATROL- YUMA SECTOR in ADAIR RANGE YUMA 4760 S US HWY 95, YUMA, AZ 85365 (NAICS 928110). OSHA activity number 345912703.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Border Patrol- Yuma Sector — free Get an email when a new federal OSHA severe-injury report for U.S. Border Patrol- Yuma Sector is published. One employer, no account, unsubscribe in one click.
Site address
ADAIR RANGE YUMA 4760 S US HWY 95
City
YUMA
State
AZ
ZIP
85365
Mailing
4035 SOUTH AVENUE A, YUMA, AZ 85365
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
850
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Repeat Gravity 1 1 instance 4 exposed
Issued
Jun 28, 2022
Abate by
Jul 11, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Range Office -   The Farberware toaster oven, used to prepare food, was plugged into a relocatable power tap, powered by the wall outlet.  Employees were exposed to electrical and/or fire hazards.  The U.S. Border Patrol was previously cited for a violation of this occupational safety and health standard or its equivalent standard [29 CFR 1910.303(b)(2)], which was contained in OSHA inspection number 1525226, citation number 1, item number 1 and was affirmed as a final order on July 16, 2021, with respect to a workplace located at 2410 Natures Path Way, Blaine, Washington 98230.  The U.S. Border Patrol was previously cited for a violation of this occupational safety and health standard or its equivalent standard [29 CFR 1910.303(b)(2)], which was contained in OSHA inspection number 1411830, citation number 1, item number 1 and was affirmed as a final order on September 10, 2019, with respect to a workplace located at 10710 N Newport Highway, Spokane, Washington 99218.
Recent events (1)
  • — Z (R) $0

1910.305 B02 I

Repeat Gravity 1 1 instance 4 exposed
Issued
Jun 28, 2022
Abate by
Jul 11, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   Range Office - The Toshiba wall air-conditioning unit, used for temperature control, was powered by a yellow flexible cord plugged into an uncovered outlet.  Employees were exposed to electrical shock hazards.  The U.S. Border Patrol Calexico Station  was previously cited for a violation of this occupational safety and health standard or its equivalent standard [29 CFR 1910.305(b)(2)(i)], which was contained in OSHA inspection number 1495425, citation number 1, item number 3, and was affirmed as a final order on February 1, 2021, with respect to a workplace located at 1699 East Carr Road, Calexico, CA 92231.
Recent events (1)
  • — Z (R) $0

1910.305 G01 IV A

Repeat Gravity 1 3 instances 4 exposed
Issued
Jun 28, 2022
Abate by
Jul 18, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure:  In the Range Office, the following appliances were plugged into flexible cords in lieu of permanent wiring:  a) The Magic Chef microwave, used to prepare food, was plugged into a red and black flexible cord, powered by the wall outlet.  b) The refrigerator, used to store food, was plugged into an orange flexible cord, powered by the wall outlet. c) The Toshiba wall air-conditioning unit, used for temperature control, was plugged into a yellow flexible cord, powered by the wall outlet.  Employees were exposed to electrical and/or fire hazards.  The U.S. Border Patrol - Tucson Sector was previously cited for a violation of this occupational safety and health standard or its equivalent standard [29 CFR 1910.305(g)(1)(iv)(A)], which was contained in OSHA inspection number 1566195, citation number 1, item number 3 and was affirmed as a final order on February 23, 2022, with respect to a workplace located at 1500 N La Quinta Road, Nogales, Arizona 85621.
Recent events (1)
  • — Z (R) $0

View U.S. Border Patrol- Yuma Sector's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345912703.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.