WEATHERFORD, TX —
OSHA Inspection: ATKORE INTERNATIONAL
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ATKORE INTERNATIONAL in 1202 N. BOWIE DR., WEATHERFORD, TX 76086 (NAICS 326122). OSHA activity number 346280217.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ATKORE INTERNATIONAL
- Site address
- 1202 N. BOWIE DR.
- City
- WEATHERFORD
- State
- TX
- ZIP
- 76086
- Mailing
- 1202 N. BOWIE DR., WEATHERFORD, TX 76086
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326122
- Employees
- 156
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.147 C04 I
- Issued
- Jan 17, 2023
- Abate by
- Feb 14, 2023
- Penalty
- Initial $15,625 · Current $10,938 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i):Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section On or about October 13, 2022 and times prior there to, alternative lockout tagout procedures for the Fabrication Bender #5 were not developed, documented and communicated to employees that performed included, but not limited to maintenance that required selected energy sources to be active during the repair and/or maintenance process as part of operational necessity in order to troubleshoot.
Recent events (2)
- — I (S) $10937.5
- — Z (S) $15625
1910.178 A04
- Issued
- Jan 17, 2023
- Penalty
- Initial $6,696 · Current $4,687 Reduced
General-duty citation text
29 CFR 1910.178(a)(4):Modifications and additions which affect capacity and safe operation of powered industrial truck were performed by the employer without the manufacturer's prior written approval. On or about October 13, 2022 and times prior thereto and thereafter, the employer was aware of unauthorized modifications to the two (2) forklift(s) in the production area and allowed operators to use the forklift(s) for purposes other than the designed and engineered operational capabilities of the powered truck by utilizing a hole in the fork to move trailers loaded with material around the facility. a) Hyster Forklift #1 b) Hyster Forklift #3
Recent events (2)
- — I (S) $4687.2
- — Z (S) $6696
1910.305 B01 II
- Issued
- Jan 17, 2023
- Penalty
- Initial $11,162 · Current $11,162
General-duty citation text
29 CFR 1910.305(b)(1)(ii):Unused openings in boxes, cabinets, or fittings were not effectively closed. On or about October 13, 2022 and times prior there to in the facility's main production area, PVC cutter Saw 19, 480v control panel cover had an unused and uncovered opening, exposing employees to electrical hazards.
Recent events (2)
- — I (O) $11162
- — Z (S) $11162
1910.147 C04 II A
- Issued
- Jan 17, 2023
- Abate by
- Feb 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(A): The energy control procedures did not contain a specific statement on the intended purpose of the procedure. On or about October 13, 2022, and times prior thereto, the employer did not ensure lockout/tagout procedures included a specific statement on the intended purpose of the procedure. Employee(s) were exposed to struck-by, caught-in, and amputation hazards. The energy control procedures did not clearly outline the purpose of the procedures for the following machines: a) Air Dryer 01 b) Centrifugal Pump c) 600 Liter Compounder d) Horizontal Cooler e) Compressor #1 f) Barrel Cooling Pump Line 1 g) Beller Line 1 h) Cool Oil Pump Line 1 i) Maplen TS-10 Line 1 j) Liquid Ring Pump EXT Vac Line 1 k) Main Feed motor line 1 l) Puller 01 m) Saw 11 n) Line 1 Vacuum Tank o) Fabrication Bender p) Fabrication Saw q) Water Circulation Pump 01 r) Trash Compactor s) Grinder 1 t) CONV DRAIN PUMP 01 u) Injection Molding Grinder v) 400 TON TOSHIBA M-1 w) Thermolator x) Cumberland Grinder 2
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.147 C06 I
- Issued
- Jan 17, 2023
- Abate by
- Feb 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i):The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed. On or about October 13, 2022 and times prior there to, an annual periodic inspection of all of the energy control procedures utilized by employees to perform required maintenance was not performed and documented by the employer on the following machines: a) Air Dryer 01 b) Centrifugal Pump c) 600 Liter Compounder d) Horizontal Cooler e) Compressor #1 f) Barrel Cooling Pump Line 1 g) Beller Line 1 h) Cool Oil Pump Line 1 i) Maplen TS-10 Line 1 j) Liquid Ring Pump EXT Vac Line 1 k) Main Feed motor line 1 l) Puller 01 m) Saw 11 n) Line 1 Vacuum Tank o) Fabrication Bender p) Fabrication Saw q) Water Circulation Pump 01 r) Trash Compactor s) Grinder 1 t) CONV DRAIN PUMP 01 u) Injection Molding Grinder v) 400 TON TOSHIBA M-1 w) Thermolator x) Cumberland Grinder 2
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.179 J02
- Issued
- Jan 17, 2023
- Abate by
- Feb 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.179(j)(2): The following items were not be inspected for defects at intervals as defined in paragraph (j)(1)(ii) of this section or as specifically indicated, including observation during operation for any defects which might appear between regular inspections: On or about October 13, 2022 and times prior there to, the overhead cranes in the facility were not being inspected on a monthly basis and were not having the hook and cable inspection being documented as required.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.179 J03
- Issued
- Jan 17, 2023
- Abate by
- Feb 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.179(j)(3):A complete periodic inspection of crane(s) had not been conducted in the past 12 months. On or about October 13, 2022 and times prior there to and there after, complete periodic inspections of the overhead cranes in the facility that are used to move production related materials had not been completed within the past twelve (12) months.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G02 III
- Issued
- Jan 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about October 10, 2022 and at times prior thereto, in the Production Area, strain relief device(s) were not provided for 110v electrical wiring entering junction box horizontally mounted on end of production line 2.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Atkore International